Technical data
EL9227-5500
EL9227-6600
EL9227-4433
EL9227-6644
EL9227-9664
EL9227-9482
Nominal voltage
24 V
DC
(-15 %/+20 %)
Nominal current
Max. Ʃ10 A, ad-
justable
Max. 4 A, ad-
justable
3 A / 3 A, fixed
4 A / 4 A, fixed
6 A / 4 A, fixed
8 A / 2 A, fixed
Nominal current steps
1, 2, 3, 4, 5, 6, 7,
8, 9, 10 A
1, 2, 3, 4 A
Input current
max. 10 A (Input current = forwarding c current of the own terminal)
Number of outputs
2
Output 1
Terminal contact and power contact
Power contacts (right)
+24 V DC protected; 0 V DC
Number of digital inputs
2 (24V DC falling edge -15% + 20%); same 0 V reference as input voltage
Prewarning output load
Adjustable between 50% and 100%, 5% hysteresis
Tripping behavior
tables showing tripping times [
Restart time
≥ 10 seconds (temperature-dependent)*
Internal fuse (faile-safe ele-
ment) (channel1/channel2)
15 A (F) / 15 A
(F)
6 A (T) / 6 A (T)
4 A (T) / 4 A (T)
6 A (T) / 6 A (T)
10 A (F) / 6 A (T) 10 A (F) / 4 A (T)
Internal max. power dissi-
pation limitation (channel1/
channel2)
typically 400 W
for 20 ms /
typically 400 W
for 20 ms
typically 160 W
for 50 ms / typi-
cally 160 W for
50 ms
typically 160 W
for 50 ms / typi-
cally 160 W for
50 ms
typically 160 W
for 50 ms / typi-
cally 160 W for
50 ms
typically 266 W
for 30 ms /
typically 160 W
for 50 ms
typically 266 W
for 30 ms /
typically 160 W
for 50 ms
Max. current limitation
(channel1/channel2)
typically 25 A for
20 ms / typically
25 A for 20 ms
typically 10 A for
50 ms / typically
10 A for 50 ms
typically 10 A for
50 ms / typically
10 A for 50 ms
typically 10 A for
50 ms / typically
10 A for 50 ms
typically 16 A for
30 ms / typically
10 A for 50 ms
typically 16 A for
30 ms / typically
10 A for 50 ms
Switch-on delay
typical 15 ms
Overcurrent protection op-
eration without E-bus
Yes
Switch-on capacitance
typically 20,000 µF**
Undervoltage prewarning
Adjustable between 17 and 24 V DC
Overvoltage shutdown
> 32 V DC
Reverse polarity switch-off
Yes
Reverse feed shutdown
U
Out
+ 1 V > U
In
Switch-off times adjustable in 3 steps (fast: after 10 ms, standard: after 100 ms, slow: after 1000 ms)
Parallel connection of sev-
eral outputs
not permissible
E-Bus current consumption typ. 80 mA
Electrical connection to
mounting rail
Yes
Measuring error
typ. ± 75 mA @23°C+- 20°C @24 V
typ. ± 150 mV @23°C+- 20°C @24 V
Electrical isolation
500 V (E-bus/signal voltage)
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
Weight
approx. 60 g
Permissible ambient tem-
perature range during oper-
ation
0°C ... + 55°C
Permissible ambient tem-
perature range during stor-
age
-25°C ... + 85°C
Permissible relative air hu-
midity
95 %, no condensation
on 35 mm mounting rail according to EN 60715
Vibration / shock resistance conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Installation position
!
Protection class
IP20
Approvals
CE
*) for further explanations see note in chapter
**) depending on: installed power supply, line resistance, load current, component tolerances, selected current range