Commissioning
EL922x
61
Version: 1.0
DIG Safe State Active
Index 0x80n0:01
DIG Safe State Value
Index 0x80n1:01
Output before bus er-
ror
Output bus error oc-
curs
TRUE
TRUE
FALSE
TRUE
TRUE
TRUE
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE / TRUE
FALSE
FALSE
TRUE
TRUE
DIG Safe State
By default, the EL922x have the DIG Safe State Active set to "FALSE".
This means that no action is executed when switching to the safe state (e.g. watchdog) and the out-
puts remain in the last state.
Please note that the terminals also perform the protection function and remain operable without
EtherCAT. Therefore, if the outputs are in the safe state, they can still be switched via the LED but-
tons and the digital inputs!
Settings via the "Settings" tab
In a more compact display, the settings can also be entered via the "Settings" tab. Proceed as follows:
• Activate the Settings input mask in the upper left corner under "
Enable Settings
" and confirm the
message box with OK. The input masks of the most common parameters are enabled.
• Select the desired channel.
• Set the desired parameters via the preselect fields (preselect xxx). The corresponding display field
(active xxx) can be found under each preselect field. The value that is currently active in the terminal is
displayed there. Use the "Apply Online" button to write modified parameters to the terminal.
• For terminals with extended functionalities (EL9227), the mode of operation can also be changed here.