![Beckhoff EL922 Series Скачать руководство пользователя страница 133](http://html1.mh-extra.com/html/beckhoff/el922-series/el922-series_documentation_2719614133.webp)
Commissioning
EL922x
133
Version: 1.0
Index
(hex)
Name
Meaning
Data type
Flags Default value
80n0:0
DIG Safe State
Active
Maximum subindex
UINT8
RO
0x01 (1
dec
)
80n0:01
Active
Enabling of the output state defined in
index 0x80n1:01 in case of a bus error
0: output retains its current state.
1: output is switched to the state defined in
index 0x80n1.
BOOLEAN RW
0x01 (1
dec
)
Index 80n1 DIG Safe State Value Ch.n
(n=2 for Ch.1; n=3 for Ch.2
Index
(hex)
Name
Meaning
Data type
Flags Default value
80n1:0
DIG Safe State
Value
Maximum subindex
UINT8
RO
0x01 (1
dec
)
80n1:01
Value
Defines the state of the output in case of a
bus error:
0: output off
1: output on
BOOLEAN RW
0x00 (0
dec
)
7.6.3.3
Command object
Index B000 Command
Index (hex) Name
Meaning
Data type
Flags
Default
B000:0
Command
Max. Subindex
UINT8
RO
0x03 (3
dec
)
B000:01
Request
Commands can be sent to the terminal via the re-
quest object
OCTET-
STRING[2]
RW
{0}
B000:02
Status
Status of the command currently being executed
• 0: Command executed without error
• 255: Command is being executed
UINT8
RO
0x00 (0
dec
)
B000:03
Response
Optional return value of the command
OCTET-
STRING[6]
RO
{0}