background image

 

CLT- & CLX-2DIM8

 

Functional Summary 

The Crestron

®

 2-Feed, 8-Dimmer Terminal Block and 

Module (CLT-2DIM8 and CLX-2DIM8, respectively), 
are considered a single entity and must be used together. 
They ship separately to permit termination of the field 
wiring to the CLT-2DIM8 prior to installation of the 
CLX-2DIM8, as described in this guide. They can be 
mounted in any Crestron Automation Enclosure (CAEN-
Series Enclosures). The terminal block is designed to 
terminate two circuit feeds (HOT and NEUTRAL) and 
distribute the controlled circuits (LOAD) to the fixtures. 
The module connects to the terminal block and performs 
dimming control of eight incandescent, magnetic low 
voltage, neon, cold cathode, or dimmable 2-wire 
fluorescent lighting loads. The maximum load is 16 amps 
for any controlled circuit, limited to 16 amps total for 
circuits 1 through 4 and 16 amps total for circuits 5 
through 8. The unit requires 120VAC 50/60 Hz, 1 phase 
input voltage. An oversize heat sink dissipates heat 
efficiently. There are LEDs on the module to indicate 
communication to a Cresnet

®

 network, input power to the 

module, and output power to the load. 

NOTE:

  The two input lines must be the same phase or 

split phase. 

NOTE:  

When connecting to an Arc Fault Breaker, the 

load should not exceed 1000 watts per breaker.  

Industry Compliance 

This product is Listed to applicable UL Standards and 
requirements by Underwriters Laboratories Inc.  

     

(E103692)

 

Installation 

The terminal block and module must be mounted into a 
Crestron Automation Enclosure by a licensed electrician, 
in accordance with all national and local codes.  

CAUTION:  

This equipment is for indoor use only 

and needs to be air-cooled. Mount in a well-
ventilated area. The ambient temperature must be 
32

°

F to 104

°

F (0

°

C to 40

°

C). The relative humidity 

must be 0% to 90% (non-condensing).  

Terminal blocks are installed along the left side of single-
wide enclosures and along the outside edges (left and 
right sides) of double-wide enclosures. Modules are 
installed along the right side of single-wide enclosures 

and side-by-side in the center of double-wide enclosures. 
When installing modules and terminal blocks in a double-
wide enclosure, be sure to invert units on the right side so 
that they can be properly wired. Refer to the illustrations 
shown in the next column when considering the location 
of terminal blocks and modules within an enclosure.  

NOTE:  

Modules and terminal blocks must be 

installed into the lowest available spaces and 
continue toward the top of the enclosure. 

Terminal Block & Module Locations (Single-wide Enclosure) 

TERMINAL

BLOCK

GROUNDING

TERMINAL

BLOCK

MODULE

 

Terminal Block & Module Locations (Double-wide Enclosure) 

Crestron Electronics, Inc.

 

Installation Guide – DOC. 6280A

 

15 Volvo Drive   Rockleigh, NJ 07647

 

(2010978)

  

Tel: 888.CRESTRON

 

01.06

   

Fax: 201.767.7576

  

Specifications subject to 

 

www.crestron.com

 

change without notice.

 

TERMINAL BLOCK

(RIGHT)

GROUNDING TERMINAL BLOCKS

TERMINAL BLOCK

(LEFT)

MODULE

 

Содержание CLT-2DIM8

Страница 1: ...ments by Underwriters Laboratories Inc E103692 Installation The terminal block and module must be mounted into a Crestron Automation Enclosure by a licensed electrician in accordance with all national and local codes CAUTION This equipment is for indoor use only and needs to be air cooled Mount in a well ventilated area The ambient temperature must be 32 F to 104 F 0 C to 40 C The relative humidit...

Страница 2: ...the modules and terminal blocks along the right side must be inverted when mounting CAUTION Bypass jumpers are installed on the terminal blocks to allow testing of circuits and to protect the module during installation When properly secured by five screws the bypass jumpers on the black and red sections of the terminal block short the hot to dim so that all circuits receive power Do not remove the...

Страница 3: ...eaker and remove the bypass jumpers on the black and red sections of the terminal block The jumpers on the white sections of the terminal block must remain installed Refer to the figures in the next column for a close up of the jumpers NOTE Before the bypass jumpers shown in the illustration are removed the Crestron Professional Automation Computer PAC2 which provides control to the system should ...

Страница 4: ... on any products returned with an RMA 3 Return freight charges following repair of items under warranty shall be paid by CRESTRON shipping by standard ground carrier In the event repairs are found to be non warranty return freight costs shall be paid by the purchaser CRESTRON Limited Warranty CRESTRON ELECTRONICS Inc warrants its products to be free from manufacturing defects in materials and work...

Отзывы: