background image

 

 

 OPA2-2T(H)-VC Operation Terminal 

Technical Data

 

  

Doc: 70-00-0379, V1.2, 20140213 

© Vector Controls GmbH, Switzerland 

Page 1 

Subject to alteration 

www.vectorcontrols.com 

OPA2-2T(H)-VC 

Operation terminal for TCX2 

Features 

 

Remote access to controller state, setpoints, inputs and outputs 

 

Access to time schedule and clock settings 

 

Access to configuration parameters 

 

RS485 peer to peer communication according to proprietary 

protocol of Vector Controls GmbH 

 

The terminal adapts itself to the TCX2 controller used. One terminal 

thus fits all the configuration variations of the TCX2 product range.  

 

Internal temperature sensor 

 

Internal humidity sensor (H version) or with AES-HT-A3 for 

example 

 

2 passive inputs: (only available with firmware version V1.1 and up)  

Applications 

 

Configuration and operation of TCX2 controllers 

 

Remote supervision (RS485) 

General Description 

The OPA2-2T(H)-VC is a remote display and operation terminal for TCX2 series controllers.  

Ordering 

Item Name 

Item Code 

Description/Option 

OPA2-2T-VC 

40-50-0047 

Operation terminal for TCX2-type controller with peer to peer RS485 

communication and internal temperature sensor and 2 passive inputs 

OPA2-2TH-VC 

40-50-0023 

As above with internal humidity sensor  

Mounting location 

 

Install the operation terminal on an easy accessible interior wall, approx. 1.5 m above the floor in an area 

of average temperature. 

 

Avoid direct sunlight or other heat sources, e.g. the area above radiators and heat emitting equipment.  

 

Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.  

 

Location of mounting is less critical if external temperature sensors are used. 

Installation 

1.

 

Connect the wires to be connected to the terminals of the power case according to wiring diagram 

2.

 

Install the mounting plate to the flush mounting box. Make sure that the nipple with the front holding screw is 

facing to the ground. Make sure the mounting screw heads do not stand out more than 5 mm (0.2”) off the 

surface of the mounting plate.  

3.

 

Ensure that the jumpers are set correctly.  

4.

 

Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting 

plate.  

5.

 

Carefully lower the front part until the interconnector reaches the mounting-plate. Continue pressing in a 

gentle way until the front part is fully connected. While inserting the connectors, a slight resistance can be felt. 
This is normal. Do not use excessive force!  

6.

 

With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the front part to 

the mounting plate. This screw is located on the front lower side of the unit. There is no need to tighten the 

screw too much. 

Dimensions [mm] (in) 

 

88 (3.5) 

32 (1.2) 

21  

(0.8) 

88 (3.5)

 

58 (2.3)

 

Содержание OPA2-2T-VC

Страница 1: ...l on an easy accessible interior wall approx 1 5 m above the floor in an area of average temperature Avoid direct sunlight or other heat sources e g the area above radiators and heat emitting equipmen...

Страница 2: ...Nominal velocity Shielded Twisted Pair STP CAT5 or CAT6 balanced 100 to 120 ohm 50 pF m 16pF ft or lower 65 or higher Environment Operation Climatic Conditions Temperature Humidity To IEC 721 3 3 cla...

Страница 3: ...mode This function is helpful for tuning the VAV system This feature may be disabled by setting UP02 to OFF While the secondary loop is displayed change the set point with UP DOWN The hand symbol appe...

Страница 4: ...ep 2 Apply selected switching time Pr01 to DAY1 Mon DAY 7 Sun While Pr01 is displayed and DAY1 is blinking Press UP Activate Pr01 switching time for DAY1 triangle appears on 1 Press DOWN Deactivate Pr...

Страница 5: ...p 3 Display total run time for binary outputs While in binary output mode Press OPTION key to display the total number of hours the binary output has been ON Large digits show in output type number Sm...

Страница 6: ...ayed UI AL LP AO FAN DO CO etc select with UP DOWN and open with OPTION Then select the ID with UP DOWN keys 1U 2U 3U etc open with OPTION As soon as the module is open its parameters are displayed 5...

Страница 7: ...lder 2 on AEC PM1 5 EEP3 External memory folder 3 on AEC PM1 6 EEP4 External memory folder 4 on AEC PM1 4 Press OPTION key Now select copy destination These are the options 1 RUN Run time memory 2 DFL...

Отзывы: