Vector OPA2-2T-VC Скачать руководство пользователя страница 7

 

 

 OPA2-2T(H)-VC Operation Terminal 

Engineering

 

  

Doc: 70-00-0379, V1.2, 20140213 

© Vector Controls GmbH, Switzerland 

Page 7 

Subject to alteration 

www.vectorcontrols.com 

Copying and restoring the entire parameter set 

It is possible to backup and refresh the entire parameter set to a second onboard memory (default memory) or a plug-

in memory. This simplifies substantially the programming of multiple controllers with identical parameter sets. 

Removable plug-in memory AEC-PM1 

The plug-in memory is an accessory that can be plugged in on the right side of the TCX2. Once connected, the power 

LED on the AEC-PM1 lights up. The memory can hold up to 4 individual parameter sets. It is easy for a site engineer to 

update a variety of standard installations or for an OEM to program his standard setup based on application.  

Auto-load 

While copying a parameter set to eeprom, the user may choose the auto-load feature. With this feature set, the 

parameters load automatically when powering up the controller. It is thus possible for a non-technical person to 

perform a parameter update by simply powering up the controller with the AEC-PM1 plugged in.  

Procedure to copy parameter sets 

1.

 

Login to engineering parameters as described above.  

2.

 

Press UP or DOWN until COPY is selected 

3.

 

Press the OPTION key. Select copy source: These are the options:  

0.

 

CLR 

 

The copy destination will be erased 

1.

 

RUN 

 

Run time memory 

2.

 

DFLT 

 

Default: On board backup memory 

3.

 

EEP1 

 

External memory folder 1 on AEC-PM1 

4.

 

EEP2 

 

External memory folder 2 on AEC-PM1 

5.

 

EEP3 

 

External memory folder 3 on AEC-PM1 

6.

 

EEP4 

 

External memory folder 4 on AEC-PM1 

4.

 

Press OPTION key. Now select copy destination: These are the options:  

1.

 

RUN 

 

Run time memory 

2.

 

DFLT 

 

Default: On board backup memory 

3.

 

EEP1 

 

External memory folder 1 on AEC-PM1 

4.

 

EEP2 

 

External memory folder 2 on AEC-PM1 

5.

 

EEP3 

 

External memory folder 3 on AEC-PM1 

6.

 

EEP4 

 

External memory folder 4 on AEC-PM1 

5.

 

Press OPTION key. Your selection is shown on the large digits: source ID to target ID. For example run time 

memory to eep1 is shown as 1to3. After confirming the selection, choose YES or AUTO to start the copy 

process. Select NO to abort. AUTO s only available if the target is the external plug in. By selecting AUTO: 

The parameters will load automatically when the controller is powered up while the AEC-PM1 is plugged in. If 

one plug-in has several parameter folders with the AUTO flag set the one with the smallest index will be 

loaded.  

 

New Feature for products with a communication plug-in. 

Selecting CO15 = 01 will write back an 

increased address to the AEC-PM1 after a successful copy. This way it is easier to configure large projects.  

 

6.

 

Press the OPTION key to conclude the selection. The Data LED on the AEC-PM1 plug-in blinks to indicate data 

communication in case it is copied to or from. PEND is shown while the copy process takes place.  

There are several possibilities for the result:  

 

Good: The copy process was successful 

 

Fail: Err5, Communication problem. The plug in module is either damaged or missing 

 

Fail: Err6, Checksum mismatch. The checksum of the source data was incorrect. Data corruption. 

This may happen if the plug-in has not been written to before or data corruption took place.  

 

Содержание OPA2-2T-VC

Страница 1: ...l on an easy accessible interior wall approx 1 5 m above the floor in an area of average temperature Avoid direct sunlight or other heat sources e g the area above radiators and heat emitting equipmen...

Страница 2: ...Nominal velocity Shielded Twisted Pair STP CAT5 or CAT6 balanced 100 to 120 ohm 50 pF m 16pF ft or lower 65 or higher Environment Operation Climatic Conditions Temperature Humidity To IEC 721 3 3 cla...

Страница 3: ...mode This function is helpful for tuning the VAV system This feature may be disabled by setting UP02 to OFF While the secondary loop is displayed change the set point with UP DOWN The hand symbol appe...

Страница 4: ...ep 2 Apply selected switching time Pr01 to DAY1 Mon DAY 7 Sun While Pr01 is displayed and DAY1 is blinking Press UP Activate Pr01 switching time for DAY1 triangle appears on 1 Press DOWN Deactivate Pr...

Страница 5: ...p 3 Display total run time for binary outputs While in binary output mode Press OPTION key to display the total number of hours the binary output has been ON Large digits show in output type number Sm...

Страница 6: ...ayed UI AL LP AO FAN DO CO etc select with UP DOWN and open with OPTION Then select the ID with UP DOWN keys 1U 2U 3U etc open with OPTION As soon as the module is open its parameters are displayed 5...

Страница 7: ...lder 2 on AEC PM1 5 EEP3 External memory folder 3 on AEC PM1 6 EEP4 External memory folder 4 on AEC PM1 4 Press OPTION key Now select copy destination These are the options 1 RUN Run time memory 2 DFL...