Commissioning
EL3773
140
Version: 2.5
Fig. 155: Global Variable List
Adaptation of the calculation of voltage and current from the raw data
The program allows the adaptation of the conversion of the raw data into the corresponding voltage and
current values. The default settings are already adapted to the EL3773 and do not absolutely have to be
changed for commissioning.
Only the transformation factor of the current transformer should be checked.
• All necessary settings for the calculation of the respective voltage and current values are made in the
MAIN. The presets correspond to the standard settings of the EL 3773
◦ rMaxVoltage specifies the maximum measuring voltage
◦ rMaxCurrent specifies the maximum measuring current
◦ iMaxRawValue specifies the raw value of the terminal at the maximum measuring voltage.
◦ The three variables
rTransformerFactor
specify the transformation factors of the current
transformers for the respective current channels
◦ Furthermore, offsets can be specified per channel. The inclusion of the offsets in the
calculation of the measured values takes place directly by means of adaptation of the
respective raw value.
Содержание EL3773
Страница 1: ...Documentation EL3773 Power Monitoring Oversampling Terminal 2 5 2018 03 13 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EL3773 6 Version 2 5...
Страница 39: ...Mounting and wiring EL3773 39 Version 2 5 Fig 29 Other installation positions...
Страница 41: ...Mounting and wiring EL3773 41 Version 2 5 Fig 31 Block diagram...
Страница 47: ...Commissioning EL3773 47 Version 2 5 Fig 38 Incorrect driver settings for the Ethernet port...
Страница 58: ...Commissioning EL3773 58 Version 2 5 Fig 57 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3...
Страница 147: ...Commissioning EL3773 147 Version 2 5 Fig 168 Confirming program start...