NOTE:  

Modules and terminal blocks must be installed 

into the lowest available spaces and continue toward the 
top of the enclosure. 

The Crestron

®

 2-Feed, 8-Dimmer Terminal Block and 

Module (CLTI-2DIM8 and CLXI-2DIM8, respectively), 
are considered a single entity and must be used together. 
They ship separately to permit termination of the field 
wiring to the CLTI-2DIM8 prior to installation of the 
CLXI-2DIM8, as described in this guide. They can be 
mounted in any Crestron Automation Enclosure (CAEN 
or CAENIB-Series Enclosures). The terminal block is 
designed to terminate two circuit feeds (LINE and 
NEUTRAL) and distribute the controlled circuits (LOAD) 
to the fixtures. The module connects to the terminal block 
and performs dimming control of eight incandescent, 
magnetic low voltage, neon, cold cathode, or dimmable  
2-wire fluorescent lighting loads. The maximum load is 
10 amps for any single controlled circuit, or 13 amps for 
each group of four circuits, and 26 amps maximum total 
per module. The unit requires 230VAC 50 Hz, 1 phase 
input voltage. An oversize heat sink dissipates heat 
efficiently. There are LEDs on the module to indicate 
communication to a Cresnet

®

 network, input power to the 

module, and output power to the load. 

Terminal Block & Module Locations (Single-wide Enclosure) 

MODULE

ROUNDING

ERMINAL

BLOCK

TERMINAL

BLOCK

(INSTALL INTO

LOWEST

AVAILABLE

SPACES)

 

NOTE:

  The two input lines must be the same phase or 

split phase. 

NOTE:  

When connecting to an Arc Fault Breaker, the 

load should not exceed 1000 watts.  

Terminal Block & Module Locations (Double-wide Enclosure) 

Installation 

The terminal block and module must be mounted into a 
Crestron Automation Enclosure by a licensed electrician, 
in accordance with all national and local codes.  

CAUTION:  

This equipment is for indoor use only and 

needs to be air-cooled. Mount in a well-ventilated area. 
The ambient temperature must be 0

°

C to 40

°

C (32

°

F to 

104

°

F). The relative humidity must be 0% to 90% (non-

condensing).  

Terminal blocks are installed along the left side of single-
wide enclosures and along the outside edges (left and 
right sides) of double-wide enclosures. Modules are 
installed along the right side of single-wide enclosures 
and side-by-side in the center of double-wide enclosures. 
When installing modules and terminal blocks in a double-
wide enclosure, be sure to invert units on the right side so 
that they can be properly wired. Refer to the illustrations 
shown in the next column when considering the location 
of terminal blocks and modules within an enclosure.  

Crestron Electronics, Inc.

 

Installation Guide – DOC. 6411A

 

15 Volvo Drive   Rockleigh, NJ 07647

 

(2013809)

   

Tel: 888.CRESTRON

 

11.07

   

Fax: 201.767.7576

  

Specifications subject to 

 

www.crestron.com

 

change without notice.

 

MODULE

TERMINAL BLOCK

(LEFT)

GROUNDING TERMINAL BLOCKS

TERMINAL BLOCK

(RIGHT)

(INSTALL INTO

LOWEST

AVAILABLE

SPACES)

 

Содержание CLTI-

Страница 1: ...DULE ROUNDING ERMINAL BLOCK TERMINAL BLOCK INSTALL INTO LOWEST AVAILABLE SPACES NOTE The two input lines must be the same phase or split phase NOTE When connecting to an Arc Fault Breaker the load should not exceed 1000 watts Terminal Block Module Locations Double wide Enclosure Installation The terminal block and module must be mounted into a Crestron Automation Enclosure by a licensed electricia...

Страница 2: ...OUP 2 FEED DIM5 DIM8 FROM 16 AMP CIRCUIT BREAKER NEUTRAL AREA FOR MODULE LOCATION LABEL TO LOAD S LEFT SIDE WIRING LABEL TERMINAL BLOCK GND GROUNDING TERMINAL BLOCK NEUTRAL GROUP 1 FEED DIM1 DIM4 FROM 16 AMP CIRCUIT BREAKER LINE 1 LINE 2 3 Use the two supplied self tapping pan Phillips screws 8B x 6 mm length to secure the terminal block to the Crestron Automation Enclosure CAUTION Bypass jumpers ...

Страница 3: ... is delivered to the loads 5 Turn off the circuit breakers and remove the bypass jumpers on the brown and red sections of the terminal block The jumpers on the blue sections of the terminal block must remain installed Refer to the figures in the next column for a close up of the jumpers NOTE Before the bypass jumpers are removed the Crestron Professional Automation Computer PAC2 which provides con...

Страница 4: ...lso log onto the online help section of the Crestron website www crestron com onlinehelp to ask questions about Crestron products First time users will need to establish a user account to fully benefit from all available features 3 Press the SETUP button again for each output 4 After turning on the last output press the SETUP button again to turn on all outputs 5 Press the SETUP button once more t...

Страница 5: ...r 90 days batteries and incandescent lamps are not covered This warranty extends to products purchased directly from CRESTRON or an authorized CRESTRON dealer Purchasers should inquire of the dealer regarding the nature and extent of the dealer s warranty if any CRESTRON shall not be liable to honor the terms of this warranty if the product has been used in any application other than that for whic...

Страница 6: ...Terminal Block Module Crestron CLTI CLXI 2DIM8 6 Terminal Block Module CLTI CLXI 2DIM8 Installation Guide DOC 6411A This page is intentionally left blank ...

Отзывы: