CLTI- & CLXI-2DIM8

 

5.  Grounding terminal blocks are available in the 

cabinet for termination of ground wires. Tighten 
to 4 Nm (2.5 - 6.0 mm

2

), 4.5 Nm (10.0 mm

2

), or 

5.1 Nm (16 - 25 mm

2

). 

Terminal Block Installation and Field 
Wiring 

NOTE: 

To install a CLTIBN Circuit Breaker Terminal 

Block, refer to the latest version of the CLTIBN 
Installation Guide (Doc. 6561) which can be downloaded 
from the Crestron website (www.crestron.com/manuals). 

6.  Test the circuit for electrical faults by turning on 

the circuit breakers, checking that the breakers 
do not trip, and that power is delivered to the 
proper loads.  

NOTE: 

Both left-side and right-side adhesive wiring 

labels are provided. The left-side labels are used in both 
single and double-wide enclosures. The right-side labels 
are only used in double-wide enclosures.  

NOTE:

  If installing in a CAENIB, complete the 

installation with a CAENIB-BP Blank Plate. Refer to the 
latest version of the CAENIB-BP Installation Guide (Doc. 
6563) for details. 

1.  Remove the backing from the left or right 

adhesive wiring label. 

Wiring Diagram of the Terminal Block to the Feed and 
Load(s)(Single-wide and Left Side Double-wide Enclosures) 

2.  Apply the adhesive label by aligning the holes in 

the label with the appropriate holes on the 
Crestron Automation Enclosure where the 
terminal block is to be mounted. For information 
on mounting locations, refer to the latest version 
of the CAEN Installation Guide (Doc. 5940) or 
the CAENIB Installation Guide (Doc. 6562). The 
wiring label lies beneath the terminal block as 
shown in the two wiring diagrams on this page. 

BYPASS

JUMPERS

GROUP 2 FEED 

(DIM5 - DIM8)

FROM 16 AMP

CIRCUIT BREAKER

NEUTRAL

AREA FOR

MODULE

LOCATION

LABEL

TO

LOAD(S)

LEFT SIDE

WIRING LABEL

TERMINAL

BLOCK

GND

GROUNDING

TERMINAL

BLOCK

NEUTRAL

GROUP 1 FEED 

(DIM1 - DIM4)

FROM 16 AMP

CIRCUIT BREAKER

LINE 1

LINE 2

 

3.  Use the two supplied self-tapping pan Phillips 

screws (8B x ¼ (6 mm) length) to secure the 
terminal block to the Crestron Automation 
Enclosure. 

CAUTION:  

Bypass jumpers are provided to allow 

testing and to protect the module during installation. 
When properly secured by five screws, the bypass 
jumpers on the brown and red sections of the terminal 
block short the 

LINE

 in to 

DIM

 out so that the 

circuit is energized. Do not remove the bypass 
jumpers until all feed and load wiring has been 
completed, the circuit has been tested for electrical 
faults, and the module has been installed. Refer to 
“Module Installation” on next page. 
 
Furthermore, the jumpers on the blue sections of the 
terminal block ties the neutral in to the neutral outs. 
These jumpers should never be removed. 

Wiring Diagram of the Terminal Block to the Feed and 
Load(s) (Right Side Double-wide Enclosures) 

GROUNDING

TERMINAL

BLOCK

GND

NEUTRAL

GROUP 2 FEED 

(DIM5 - DIM8)

FROM 16 AMP

CIRCUIT BREAKER

AREA FOR

MODULE

LOCATION

LABEL

WIRING LABEL

RIGHT SIDE

BLOCK

TERMINAL

TO

LOAD(S)

NEUTRAL

GROUP 1 FEED 

(DIM1 - DIM4)

FROM 16 AMP

CIRCUIT BREAKER

BYPASS

JUMPERS

LINE 2

LINE 1

 

NOTE:  

Use copper conductors only – rated 75

°

4.  With the circuit breakers turned off, connect the 

circuit feed (LINE and NEUTRAL) and 
controlled circuit (LOAD) wires to the terminal 
block per the markings provided on the wiring 
label (as shown in the diagrams on this page). 
Terminal blocks accept one 2.5 - 6.0 mm

2

 wire. 

Wires should be stripped to 12 mm. Tighten 
terminal blocks to 1 Nm.  

2  

  Terminal Block & Module:  CLTI- & CLXI-2DIM8 

Installation Guide – DOC. 6411A 

Содержание CLTI-

Страница 1: ...DULE ROUNDING ERMINAL BLOCK TERMINAL BLOCK INSTALL INTO LOWEST AVAILABLE SPACES NOTE The two input lines must be the same phase or split phase NOTE When connecting to an Arc Fault Breaker the load should not exceed 1000 watts Terminal Block Module Locations Double wide Enclosure Installation The terminal block and module must be mounted into a Crestron Automation Enclosure by a licensed electricia...

Страница 2: ...OUP 2 FEED DIM5 DIM8 FROM 16 AMP CIRCUIT BREAKER NEUTRAL AREA FOR MODULE LOCATION LABEL TO LOAD S LEFT SIDE WIRING LABEL TERMINAL BLOCK GND GROUNDING TERMINAL BLOCK NEUTRAL GROUP 1 FEED DIM1 DIM4 FROM 16 AMP CIRCUIT BREAKER LINE 1 LINE 2 3 Use the two supplied self tapping pan Phillips screws 8B x 6 mm length to secure the terminal block to the Crestron Automation Enclosure CAUTION Bypass jumpers ...

Страница 3: ... is delivered to the loads 5 Turn off the circuit breakers and remove the bypass jumpers on the brown and red sections of the terminal block The jumpers on the blue sections of the terminal block must remain installed Refer to the figures in the next column for a close up of the jumpers NOTE Before the bypass jumpers are removed the Crestron Professional Automation Computer PAC2 which provides con...

Страница 4: ...lso log onto the online help section of the Crestron website www crestron com onlinehelp to ask questions about Crestron products First time users will need to establish a user account to fully benefit from all available features 3 Press the SETUP button again for each output 4 After turning on the last output press the SETUP button again to turn on all outputs 5 Press the SETUP button once more t...

Страница 5: ...r 90 days batteries and incandescent lamps are not covered This warranty extends to products purchased directly from CRESTRON or an authorized CRESTRON dealer Purchasers should inquire of the dealer regarding the nature and extent of the dealer s warranty if any CRESTRON shall not be liable to honor the terms of this warranty if the product has been used in any application other than that for whic...

Страница 6: ...Terminal Block Module Crestron CLTI CLXI 2DIM8 6 Terminal Block Module CLTI CLXI 2DIM8 Installation Guide DOC 6411A This page is intentionally left blank ...

Отзывы: