Commissioning
EL3773
70
Version: 2.5
Fig. 83: Configuring the process data
Note
Manual modification of the process data
According to the ESI description, a PDO can be identified as “fixed” with the flag “F” in the
PDO overview (Fig.
“Configuring the process data”
, J). The configuration of such PDOs
cannot be changed, even if TwinCAT offers the associated dialog (“Edit”). In particular, CoE
content cannot be displayed as cyclic process data. This generally also applies in cases
where a device supports download of the PDO configuration, “G”. In case of incorrect con-
figuration the EtherCAT slave usually refuses to start and change to OP state. The System
Manager displays an “invalid SM cfg” logger message: This error message (“invalid SM IN
cfg” or “invalid SM OUT cfg”) also indicates the reason for the failed start.
can be found at the end of this section.
„Startup“ tab
The
Startup
tab is displayed if the EtherCAT slave has a mailbox and supports the
CANopen over EtherCAT
(CoE) or
Servo drive over EtherCAT
protocol. This tab indicates which download requests are sent to the
mailbox during startup. It is also possible to add new mailbox requests to the list display. The download
requests are sent to the slave in the same order as they are shown in the list.
Содержание EL3773
Страница 1: ...Documentation EL3773 Power Monitoring Oversampling Terminal 2 5 2018 03 13 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EL3773 6 Version 2 5...
Страница 39: ...Mounting and wiring EL3773 39 Version 2 5 Fig 29 Other installation positions...
Страница 41: ...Mounting and wiring EL3773 41 Version 2 5 Fig 31 Block diagram...
Страница 47: ...Commissioning EL3773 47 Version 2 5 Fig 38 Incorrect driver settings for the Ethernet port...
Страница 58: ...Commissioning EL3773 58 Version 2 5 Fig 57 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3...
Страница 147: ...Commissioning EL3773 147 Version 2 5 Fig 168 Confirming program start...