Appendix
EL3773
173
Version: 2.5
Fig. 186: Selecting the
Restore default parameters
PDO
Double-click on SubIndex 001 to enter the Set Value dialog. Enter the value
1684107116
in field
Dec
or the
value
0x64616F6C
in field
Hex
and confirm with
OK
(Fig.
Entering a restore value in the Set Value dialog
).
All backup objects are reset to the delivery state.
Fig. 187: Entering a restore value in the Set Value dialog
Note
Alternative restore value
In some older terminals the backup objects can be switched with an alternative restore
value: Decimal value: 1819238756, Hexadecimal value: 0x6C6F6164An incorrect entry for
the restore value has no effect.