Assembly
Fig. 25: Attaching on mounting rail
The bus coupler and bus terminals are attached to commercially available 35 mm mounting rails (DIN rails
according to EN 60715) by applying slight pressure:
1. First attach the fieldbus coupler to the mounting rail.
2. The bus terminals are now attached on the right-hand side of the fieldbus coupler. Join the compo-
nents with tongue and groove and push the terminals against the mounting rail, until the lock clicks
onto the mounting rail.
If the terminals are clipped onto the mounting rail first and then pushed together without tongue and
groove, the connection will not be operational! When correctly assembled, no significant gap should
be visible between the housings.
Fixing of mounting rails
The locking mechanism of the terminals and couplers extends to the profile of the mounting rail. At
the installation, the locking mechanism of the components must not come into conflict with the fixing
bolts of the mounting rail. To mount the mounting rails with a height of 7.5 mm under the terminals
and couplers, you should use flat mounting connections (e.g. countersunk screws or blind rivets).
Содержание EL3413-0000
Страница 1: ...Documentation EL34x3 3 phase power measurement terminal 4 4 2019 03 28 Version Date ...
Страница 2: ......
Страница 6: ...Table of contents EL34x3 6 Version 4 4 ...
Страница 47: ...Installation EL34x3 47 Version 4 4 Fig 33 Other installation positions ...
Страница 91: ...Commissioning EL34x3 91 Version 4 4 Fig 88 Incorrect driver settings for the Ethernet port ...
Страница 102: ...Commissioning EL34x3 102 Version 4 4 Fig 107 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3 ...