Commissioning
EL34x3
162
Version: 4.4
Index 6030 PM Inputs Auxiliary
Index (hex) Name
Meaning
Data type
Flags
Default
6030:0
PM Inputs Ch.3
Largest subindex of this object
UINT8
RO
>19<
6030:03
Overcurrent
Overcurrent
BOOLEAN
RO
0x00 (0
dec
)
6030:0F
TxPDO State
TRUE for general error
BOOLEAN
RO
0x00 (0
dec
)
6030:10
TxPDO Toggle
The TxPDO toggle is toggled by the slave when the data
of the associated TxPDO is updated.
BOOLEAN
RW
0x00 (0
dec
)
6030:11
Index
Acknowledges for auxiliary variables (see following table) UINT8
RW
0x00 (0
dec
)
6030:12
Channel
UINT8
RW
0x00 (0
dec
)
6030:13
Value
variable output value Aux channel (
INT32
RW
0x00000000
(0
dec
)
Channel
(dec)
Index (dec)
Name
Unit
0
0
Neutral conductor current
0.000001 A
0
2
Sum of the energy (channel 1-3)
0.001 Wh
0
4
Frequency
0.1 Hz
0
5
Sum of the energy (negative) (channel 1-3)
(absolute value)
0.001 Wh
0
10
Sum of the active power (channel 1-3)
0.01 W
0
11
Sum of the apparent power (channel 1-3)
0.01 VA
0
12
Sum of the reactive power (channel 1-3)
0.01 var
0
20***
Active power fundamental (P1)
0.01 W
0
21***
Apparent power fundamental (S1)
0.01 VA
0
22***
Reactive power fundamental (Q1)
0.01 var
0
30****
Energy positive
0.001 Wh
0
31****
Positive energy, automatically saved
0.001 Wh
0
32****
Energy, automatic saved
0.001 Wh
0
35****
Energy negative, automatically saved
(absolute value)
0.001 Wh
0
44***
Frequency average resolution
0.01 Hz
0
45***
Frequency high resolution
0.001 Hz
0
46*****
Held frequency
0.1 Hz
0
47*****
Held frequency average resolution
0.01 Hz
0
48*****
Held frequency high resolution
0.001 Hz
0
100
ADC temperature
0.1
℃
1..3
0
Calculation ongoing
1..21
RMS value of the xth harmonic (current)
0.000001 A
51..71
Ratio of the xth harmonic to the fundamental (current)
0.01%
100
Calculation ongoing
101..121
RMS value of the xth harmonic (voltage)
0.0001 V
151..171
Ratio of the xth harmonic to the fundamental (voltage)
0.01%
11..13
0
Apparent power of phase x
0.01 VA
1
Reactive power of phase x
0.01 var
2
Energy of phase x
0.001 Wh
3
Power factor of phase x
0.001
4
Frequency of phase x
0.1 Hz
5
Energy (negative) of phase x
(absolute value)
0.001 Wh
6
Angle α between phase x and phase 1
0.01 °
10
Active power of phase x
0.01 W
11
Current of phase x
0.000001 A
12
Voltage of phase x
0.0001 V
20***
Active power fundamental (P1)
0.01 W
21***
Apparent power fundamental (S1)
0.01 VA
22***
Reactive power fundamental (Q1)
0.01 var
23***
Cos Phi = P
fund
/ S
fund
with sign from Q1
0.0001
44***
Held frequency average resolution
0.01 Hz
45***
Held frequency high resolution
0.001 Hz
Содержание EL3413-0000
Страница 1: ...Documentation EL34x3 3 phase power measurement terminal 4 4 2019 03 28 Version Date ...
Страница 2: ......
Страница 6: ...Table of contents EL34x3 6 Version 4 4 ...
Страница 47: ...Installation EL34x3 47 Version 4 4 Fig 33 Other installation positions ...
Страница 91: ...Commissioning EL34x3 91 Version 4 4 Fig 88 Incorrect driver settings for the Ethernet port ...
Страница 102: ...Commissioning EL34x3 102 Version 4 4 Fig 107 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3 ...