Product overview
EL34x3
18
Version: 4.4
2.1.2
Technical data
Technical data
EL3413-0000
EL3413-0001
EL3413-0120
Measured values
Current, voltage, effective power, apparent power, frequency
Calculated values
Reactive power, energy, power factor (cosφ), harmonic frequencies,
phase angle
Measuring voltage
max. 690 V AC 3~
(UL
X
-N: max. 400 V AC)
max. 600 V AC 3~
(UL
X
-N: max. 346 V AC)
max. 210 V AC 3~
(UL
X
-N: max. 120 V AC)
Fed-in voltages must comply with overvoltage category II
Measuring current
max. 5 A (AC) (configurable), via measuring transformer x A / 5 A
Input resistance voltage circuit
(typ.)
1 MΩ
Input resistance current circuit
(typ.)
< 3 mΩ
Fuse protection
Voltage circuit: according to the connected conductor size
Current circuit: primary side of the current transformer, according to the
connected conductor size
Resolution
0.1 µA, 0.1 mV, 10 mW
(0.1 A measuring
range)
1 µA, 0.1 mV, 10 mW
(1 A measuring range)
5 µA, 0.1 mV, 10 mW
(5 A measuring range)
1 µA, 0.1 mV, 10 mW
(1 A measuring range)
5 µA, 0.1 mV, 10 mW
(5 A measuring range)
0.1 µA, 0.1 mV, 10 mW
(0.1 A measuring
range)
1 µA, 0.1 mV, 10 mW
(1 A measuring range)
5 µA, 0.1 mV, 10 mW
(5 A measuring range)
Measuring accuracy
0.5% in relation to the full scale value (U/I),
1% calculated value (P)
Notice:
For the EL3413, an accuracy of 2% FSV (full scale value) of the largest
measuring range of the terminal is valid referring to the neutral conductor
current measurement. The neutral conductor current measurement is only
possible for this measuring range.
Frequency range
45 Hz to 65 Hz
Signal type
any (taking into account the frequency range and the limit frequency)
Measuring procedure
True RMS calculation with 16,800 (2,800 per channel) samples/s
Measuring cycle time
200 ms per measured value preset, freely configurable, mains-
synchronous
Electrical isolation
4500 V (connection terminal/E-bus)
Supply voltage for electronic
via the E-bus
E-Bus current consumption
typ. 160 mA
Configuration
via TwinCAT System Manager
Dimensions (W x H x D)
approx. 27 mm x 100 mm x 70 mm (width aligned: 24 mm)
Weight
approx. 75 g
on 35 mm mounting rail conforms to EN 60715
Operating temperature
-25°C ... +60°C (extended temperature range)
Storage temperature
-40°C ... +85°C
Relative humidity
95 % no condensation
Vibration/shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protect. class / installation pos.
IP20/any
Approvals
CE
CE
CE
Содержание EL3413-0000
Страница 1: ...Documentation EL34x3 3 phase power measurement terminal 4 4 2019 03 28 Version Date ...
Страница 2: ......