Product overview
EL34x3
17
Version: 4.4
Fig. 11: EL3413-0120
3-Phase Power Measurement Terminal
The EL3413 EtherCAT power measurement terminal is a further development of the EL3403. With up to
690 V AC the voltage inputs are optimized for direct monitoring of high-performance generators, as used in
the wind power industry, for sample.
The full scale value for the current can be set to 0.1 A, 1 A or 5 A via the CoE directory.
No upstream voltage transformer is required. The current inputs are electrically isolated so that the terminal
can be used in all common grounded current transformer configurations such as 2- or 3-transformer
configurations with star or delta connection.
Like all measured terminal data, the harmonic content can be read via the process data.
The EL3413-0001 has a maximum input voltage of 600 V AC and is additionally UL-certified.
In the case of the EL3413-0120 the voltage range is limited to 210 V AC.
Quick links
•
• Basic function principles EL34x3 [
•
CoE object description and parameterization [
•
Содержание EL3413-0000
Страница 1: ...Documentation EL34x3 3 phase power measurement terminal 4 4 2019 03 28 Version Date ...
Страница 2: ......
Страница 6: ...Table of contents EL34x3 6 Version 4 4 ...
Страница 47: ...Installation EL34x3 47 Version 4 4 Fig 33 Other installation positions ...
Страница 91: ...Commissioning EL34x3 91 Version 4 4 Fig 88 Incorrect driver settings for the Ethernet port ...
Страница 102: ...Commissioning EL34x3 102 Version 4 4 Fig 107 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3 ...