Commissioning
EL34x3
171
Version: 4.4
Index 1C32 SM output parameter
Index (hex) Name
Meaning
Data type
Flags
Default
1C32:0
SM output parameter Synchronization parameters for the outputs
UINT8
RO
>32<
1C32:01
Sync mode
Current synchronization mode:
• 0: Free Run
• 1: Synchron with SM 2 Event
• 2: DC-Mode - Synchron with SYNC0 Event
• 3: DC-Mode - Synchron with SYNC1 Event
UINT16
RW
0x0000 (0
dec
)
1C32:02
Cycle time
Cycle time (in ns):
• Free Run: Cycle time of the local timer
• Synchron with SM 2 Event: Master cycle time
• DC mode: SYNC0/SYNC1 Cycle Time
UINT32
RW
0x000AAE60
(700000
dec
)
1C32:03
Shift time
Time between SYNC0 event and output of the outputs (in
ns, DC mode only)
UINT32
RW
0x00000000
(0
dec
)
1C32:04
Sync modes sup-
ported
Supported synchronization modes:
• Bit 0 = 1: free run is supported
• Bit 1 = 1: Synchronous with SM 2 event is
supported
• Bit 2-3 = 01: DC mode is supported
• Bit 4-5 = 10: Output shift with SYNC1 event (only
DC mode)
• Bit 14 = 1: dynamic times (measurement through
)
UINT16
RW
0x0001 (1
dec
)
1C32:05
Minimum cycle time
Minimum cycle time (in ns)
UINT32
RW
0x000AAE60
(700000
dec
)
1C32:06
Calc and copy time
Minimum time between SYNC0 and SYNC1 event (in ns,
DC mode only)
UINT32
RW
0x00000000
(0
dec
)
1C32:08
Command
• 0: Measurement of the local cycle time is stopped
• 1: Measurement of the local cycle time is started
,
,
are updated with the maximum mea-
sured values.
For a subsequent measurement the measured values
are reset
UINT16
RW
0x0000 (0
dec
)
1C32:09
Delay time
Time between SYNC1 event and output of the outputs (in
ns, DC mode only)
UINT32
RW
0x00000000
(0
dec
)
1C32:0B
SM event missed
counter
Number of missed SM events in OPERATIONAL (DC
mode only)
UINT166
RW
0x0000 (0
dec
)
1C32:0C
Cycle exceeded
counter
Number of occasions the cycle time was exceeded in
OPERATIONAL (cycle was not completed in time or the
next cycle began too early)
UINT16
RW
0x0000 (0
dec
)
1C32:0D
Shift too short counter Number of occasions that the interval between SYNC0
and SYNC1 event was too short (DC mode only)
UINT16
RW
0x0000 (0
dec
)
1C32:20
Sync error
The synchronization was not correct in the last cycle
(outputs were output too late; DC mode only)
BOOLEAN
RW
0x00 (0
dec
)
Содержание EL3413-0000
Страница 1: ...Documentation EL34x3 3 phase power measurement terminal 4 4 2019 03 28 Version Date ...
Страница 2: ......
Страница 6: ...Table of contents EL34x3 6 Version 4 4 ...
Страница 47: ...Installation EL34x3 47 Version 4 4 Fig 33 Other installation positions ...
Страница 91: ...Commissioning EL34x3 91 Version 4 4 Fig 88 Incorrect driver settings for the Ethernet port ...
Страница 102: ...Commissioning EL34x3 102 Version 4 4 Fig 107 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3 ...