Commissioning
EL34x3
164
Version: 4.4
Index F010 Module list
Index (hex) Name
Meaning
Data type
Flags
Default
F010:0
Module list
Largest subindex of this object
UINT8
RO
>4<
F010:01
Subindex 001
MDP Profile 340
UINT32
RW
0x00000154
(340
dec
)
F010:02
Subindex 002
MDP Profile 340
UINT32
RW
0x00000154
(340
dec
)
F010:03
Subindex 003
MDP Profile 340
UINT32
RW
0x00000154
(340
dec
)
F010:04
Subindex 004
MDP Profile 341
UINT32
RW
0x00000155
(341
dec
)
Index 9000 PM Persistent data Ch.1
Index (hex) Name
Meaning
Data type
Flags
Default
9000:0
PM Persistent data
Ch.1
Largest subindex of this object
UINT8
RO
>4<
9000:01
Energy (overall)
stored energy value of channel 1
(1)
Unit:
0.001 Wh
INT32
RO
0x00000000
(0
dec
)
9000:02
Energy (negative)
stored negative energy value of channel 1
(1)
Unit:
0.001 Wh
INT32
RO
0x00000000
(0
dec
)
9000:03
Energy (overall) au-
tosaved
automatically saved energy value of channel 1
(1)
Unit:
0.001 Wh
INT32
RO
0x00000000
(0
dec
)
9000:04
Energy (negative) au-
tosaved
automatically saved negative energy value of channel 1
(1)
Unit:
0.001 Wh
INT32
RO
0x00000000
(0
dec
)
Index 9010 PM Persistent data Ch.2
Index (hex) Name
Meaning
Data type
Flags
Default
9010:0
PM Persistent data
Ch.2
Largest subindex of this object
UINT8
RO
>4<
9010:01
Energy (overall)
stored energy value of channel 2
(1)
Unit:
0.001 Wh
INT32
RO
0x00000000
(0
dec
)
9010:02
Energy (negative)
stored negative energy value of channel 2
(1)
Unit:
0.001 Wh
INT32
RO
0x00000000
(0
dec
)
9010:03
Energy (overall) au-
tosaved
automatically saved energy value of channel 2
(1)
Unit:
0.001 Wh
INT32
RO
0x00000000
(0
dec
)
9010:04
Energy (negative) au-
tosaved
automatically saved negative energy value of channel 2
(1)
Unit:
0.001 Wh
INT32
RO
0x00000000
(0
dec
)
Index 9020 PM Persistent data Ch.3
Index (hex) Name
Meaning
Data type
Flags
Default
9020:0
PM Persistent data
Ch.3
Largest subindex of this object
UINT8
RO
>4<
9020:01
Energy (overall)
stored energy value of channel 3
(1)
Unit:
0.001 Wh
INT32
RO
0x00000000
(0
dec
)
9020:02
Energy (negative)
stored negative energy value of channel 3
(1)
Unit:
0.001 Wh
INT32
RO
0x00000000
(0
dec
)
9020:03
Energy (overall) au-
tosaved
automatically saved energy value of channel 3
(1)
Unit:
0.001 Wh
INT32
RO
0x00000000
(0
dec
)
9020:04
Energy (negative) au-
tosaved
automatically saved negative energy value of channel 3
(1)
Unit:
0.001 Wh
INT32
RO
0x00000000
(0
dec
)
(1)
The energy values can be saved/deleted using the command object (
). The
negative energy value is the value generated by a negative power (generator mode). The energy value in the
variant value for index 3 sets is composed of generated and consumed energy, i.e. in generator mode this
value becomes smaller. The two values must be combined in order to calculate the positive energy.
From FW 10 the positive energy can be called up via the variant value indices 30/31 (see table in chapter
“
Содержание EL3413-0000
Страница 1: ...Documentation EL34x3 3 phase power measurement terminal 4 4 2019 03 28 Version Date ...
Страница 2: ......
Страница 6: ...Table of contents EL34x3 6 Version 4 4 ...
Страница 47: ...Installation EL34x3 47 Version 4 4 Fig 33 Other installation positions ...
Страница 91: ...Commissioning EL34x3 91 Version 4 4 Fig 88 Incorrect driver settings for the Ethernet port ...
Страница 102: ...Commissioning EL34x3 102 Version 4 4 Fig 107 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3 ...