Commissioning
EL34x3
153
Version: 4.4
5.7.2
Configuration data
Index 8027 PM Settings
Index (hex) Name
Meaning
Data type
Flags
Default
8027:0
PM Settings
Value
Description
UINT8
RO
>40<
8027:03
Measuring
mode
Measuring method
0
3-wire connection delta, 4-
wire connection star
BIT2
RW
0x00 (0
dec
)
1
reserved
2
reserved
8027:19*
Current range Current measuring
range
0
1 A
BIT4
RW
0x00 (0
dec
)
1
0.1 A (presently not active)
2
5 A
8027:28
External CT
phase Offset
Correction of the phase
shift of external current
transformers
The value can be entered within a
range of -0.5 radian to +0.5 radian.
1 radian corresponds to 180/φ.
Input value =
Δ φ[°] / (90/ π) x 32767
UINT16
RW
0x000A (0
dec
)
*) this object is still supported, but no longer displayed in the CoE. It is preferable to object 0x802D:11.
Index 802D PM Device Settings
Index (hex) Name
Meaning
Data type
Flags
Default
802D:0
PM Device
Settings
Largest subindex of this object
UINT8
RO
>18<
802D:11
Current
Range
Current measuring range
(EL3413)
10: 100 mA
100: 1 A
500: 5 A
Current measuring range
(EL3433)
20: 200 mA
200: 2 A
1000: 10 A
BIT4
RW
2 A (200)
802D:12
Power calcu-
lation thresh-
old
Calculation threshold for power measurement
1: 1%
2: 2%
3: 4%
4: 8%
BIT4
RW
off (0 %)
5.7.3
Command object
Index FB00 PM Command
The command object is used for triggering an action in the terminal. The command is started by writing
subindex 1 (request). Write access is disabled until the current command is completed.
Содержание EL3413-0000
Страница 1: ...Documentation EL34x3 3 phase power measurement terminal 4 4 2019 03 28 Version Date ...
Страница 2: ......
Страница 6: ...Table of contents EL34x3 6 Version 4 4 ...
Страница 47: ...Installation EL34x3 47 Version 4 4 Fig 33 Other installation positions ...
Страница 91: ...Commissioning EL34x3 91 Version 4 4 Fig 88 Incorrect driver settings for the Ethernet port ...
Страница 102: ...Commissioning EL34x3 102 Version 4 4 Fig 107 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3 ...