Product overview
EL34x3
24
Version: 4.4
• effective power P
• effective voltage U
• effective current I
• apparent power S
• reactive power Q
• power factor cos φ
• harmonic
• phase shift λ
2.3.5
Sign for power measurement
The sign of the active power P and of the power factor cos φ provide about information the direction of the
energy flow. A positive sign indicates the motor mode, a negative sign indicates generator mode.
In addition, the sign of the reactive power Q indicates the direction of the phase shift between current and
voltage. Fig.
Four-quadrant representation of active/reactive power in motor and generator mode
illustrates
this. In motor mode (quadrant I & IV) a positive reactive power indicates an inductive load, a negative
reactive power indicates a capacitive load. In generator mode (quadrant II & III), an inductive acting
generator is indicated by a positive reactive power, a capacitive acting generator by a negative reactive
power.
Fig. 16: Four-quadrant representation of active/reactive power in motor and generator mode