Error handling and diagnostics
CXxxxx-M510/B510
73
Version: 1.0
6
Error handling and diagnostics
6.1
Diagnostic LEDs
The diagnostic LEDs of a CANopen master and CANopen slaves are described here. The labelling of the
diagnostic LEDs on a CX2500 fieldbus module and an Embedded PC with optional interface is identical.
The LED description therefore only distinguishes between CANopen master and CANopen slave.
M510 (master)
Display
LED
Color
Meaning
RUN
Green
CAN is OK
Red
CAN in BUS off
Green 200 ms / Red 200
ms
CAN warning
Green and red flashing
rapidly
Baud rate search active
Green off / Red on
CAN not configured
ERR
Green on / Red off
All nodes have NodeState
= 0
Green 200 ms / Red 200
ms
All boxes in OP state, but
the tasks have not yet
started
Green off / Red 200 ms
Not all nodes in OP
Green off / Red on
No boxes configured
B510 (slave)
Display
LED
Color
Meaning
CAN
Shows the CAN status
Green
CAN is OK
Red
CAN in BUS off
Green 200 ms / Red 200
ms
CAN warning
Green and red flashing
rapidly
Baud rate search active
Green off / Red on
CAN not configured
Tx/Rx
Indicates CAN errors
Green on
Everything OK
Green 200 ms / Red 200
ms
All boxes in OP state, but
the task has not yet
started
Red 200 ms
Not all boxes in OP
Green off / Red on
No boxes configured