Connection and cabling
CXxxxx-M510/B510
29
Version: 1.0
• CSA AWM I/II A/B 80°C 300V FT1
• corresponds to the DeviceNet "Thin Cable" specification
Shielding
The screen is to be connected over the entire length of the bus cable, and only galvanically grounded at one
point, in order to avoid ground loops.
The design of the screening, in which HF interference is diverted through R/C elements to the mounting rail
assumes that the rail is appropriately earthed and free from interference. If this is not the case, it is possible
that HF interference will be transmitted from the mounting rail to the screen of the bus cable. In that case the
screen should not be attached to the couplers - it should nevertheless still be fully connected through.
Cable colors
Recommended application of Beckhoff CAN cables:
Function
ZB5100 cable color
ZB5200 cable color
CAN Ground
black/
(red)
black
CAN Low
black
blue
Shield
Filler strand
Filler strand
CAN high
white
white
not used
(red)
(red)