Drop lines
Drop lines must always be avoided as far as possible, since they inevitably cause reflections. The reflections
caused by drop lines are not however usually critical, provided they have decayed fully before the sampling
time. In the case of the bit timing settings selected in the Bus Couplers it can be assumed that this is the
case, provided the following drop line lengths are not exceeded:
Baud rate
Drop line length
Total length of all drop lines
1 Mbit/s
< 1m
< 5 m
500 kbit/s
< 5 m
< 25 m
250 kbit/s
< 10 m
< 50 m
125 kbit/s
< 20 m
< 100 m
50 kbit/s
< 50 m
< 250 m
Drop lines must not have terminating resistors.