P170
SI
state
Write-access to the drive parameters is managed via parameter M communication source
(P126) in the drive manager. The drive parameter can only be altered via the service interface
when bit no. 0 of this parameter is set to 1. If the bit is set to 0 write-access is inhibited and
only read-access to the parameter values granted.
See also M communication source (P126)
P171
SI
baud rate
The service baud rate can only be displayed and is set to a fixed value of 9600 baud.
Error number
Meaning
0
No fault
1
Element is not available
2
Datum is too short
3
Datum is too long
4
Datum is not alterable
5
Parameter is write protected
6
Datum is smaller than minimum value
7
Datum is greater than maximum value
8
Datum is invalid
9
Obtaining of parameter is invalid
Parameter
Name
Range
min. ... max.
Unit
Display
only
P170
SI
state
0000 ... FFFF
!
P171
SI
baud rate
50 ... 19200
Baud
!
P172
SI
mode
0000 ... 0003
Bit no.
Meaning
0 ... 3
status of function module
0001: RUN (all parameters can be read and write)
0000: STOP (all parameters can be read only)
11 ... 15
reserved
Содержание BUS 6 VC
Страница 1: ...E 5 03047 01 Manual V Controller BUS 6 VC Specification Digital Control BUC ...
Страница 4: ...Dokument Nr Document No 5 04058 01 Baumüller Nürnberg GmbH ...
Страница 8: ...6 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Страница 14: ...Technical Data 12 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Страница 16: ...Transportation Unpacking 14 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Страница 92: ...Parameter 90 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Страница 108: ...Appendix 106 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Страница 109: ......