Parameter
V-Controller (BUS 6 VC)
79
Baumüller Nürnberg Electronic GmbH & Co. KG
5.03047.01
Parameter description
P338
AO
state
Display of internal function module state.
P337
AO
test value
The analog output (DA converter) can be tested via this parameter.
e.g.
AO 1 source Pxxx
P330 = 337
AO test value
P337 = +10
→
analog output 1 = + 10 V
AO 1 scaling
P332 = -2000
→
analog output 1 = - 5 V
AO offset channel 1 P331 = 14000
→
analog output 1 = + 2 V
P330
AO
1 source Pxxx
P334
AO
2 source Pxxx
The output parameter numbers are entered here.
The respective channel is switched off, if this parameter is equal 0.
If a 32 bit parameter is programmed on one channel, the low word of this parameter is trans-
mitted. To transmit the high word, both channels (P330 and P334) must be programmed to
the same parameter. As a result channel 1 transmits the low word and channel 2 the high
word of the 32 bit parameter. Is channel 1 programmed to another parameter then channel 2
transmits the low word. That means that the high word of a parameter can´t be transmitted
separately without the low word. Channel 1 transmits always the low word and channel 2
transmits always the high word.
P331
AO
1 offset
P335
AO
2 offset
The offset of the analog outputs is set here.
P332
AO
1 scaling
P336
AO
2 scaling
A scaling factor can also be selected for optimum parameter output. The respective channel
is switched off, if this parameter is equal 0.
Bit no.
Meaning
0
0: STOP, analog output 1 switched off
1: RUN, analog output 1 is active
1 ... 3
reserved
4
analog output 1 at negative threshold (-10V) (X26:7)
5
analog output 1 at positive threshold (+10V) (X26:7)
8
0: STOP, analog output 2 switched off
1: RUN, analog output 2 is active
9...11
reserved
12
analog output 2 at negative threshold (-10V) (X26:8)
13
analog output 2 at positive threshold (+10V) (X26:8)
14 ... 15
reserved
Содержание BUS 6 VC
Страница 1: ...E 5 03047 01 Manual V Controller BUS 6 VC Specification Digital Control BUC ...
Страница 4: ...Dokument Nr Document No 5 04058 01 Baumüller Nürnberg GmbH ...
Страница 8: ...6 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Страница 14: ...Technical Data 12 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Страница 16: ...Transportation Unpacking 14 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Страница 92: ...Parameter 90 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Страница 108: ...Appendix 106 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Страница 109: ......