BE1-51/27R - Functional Description
3-5
held open by the installed connection plug. When the relay is removed from service by removing the
connection plug, the shorting bars are closed.
Target Indicator Circuits
When specified, a front panel target indicator for each type of monitoring (i.e., time overcurrent or instan-
taneous) will be supplied. Two types of target drive circuits are available:
Internally Operated Targets
Outputs from the overcurrent elements are directly applied to drive the appropriate target indicator. Each
indicator is tripped regardless of the current level of the trip circuit.
Current Operated Targets
This target will operate only when a minimum of 0.2 A flows in the output circuit. A special reed relay in
series with the output contact provides the signal to the target indicator.
Note that the front panel function targets (TIMED, INST 1, etc.) may be of either type. Phase and neutral
indicators are current operated only if the instantaneous options are not included and if current operated
targets are specified.
Each target, when operated, is magnetically latched and must be reset manually. Target configurations for
the various models are provided in Section 2.
Содержание BE1-51/27R
Страница 14: ...BE1 51 27R General Information 1 9 Figure 1 1 Style Number Identification Chart...
Страница 36: ...BE1 51 27R General Information 1 31 Figure 1 38 Timing Type E7 BS 142 Extremely Inverse Drawing No 99 1097...
Страница 54: ...2 2 BE1 51 27R Human Machine Interface Controls And Indicators Figure 2 1 Location of Controls and Indicators...
Страница 59: ...3 2 BE1 51 27R Functional Description Figure 3 1 Functional Block Diagram...
Страница 69: ...BE1 51 27R Installation 4 7 Figure 4 8 Typical Internal Diagram Sensing Input Type M or N...
Страница 76: ...4 14 BE1 51 27R Installation Figure 4 14 Relay Signals and Current Pickup Example For 3 Phase Fault XE 0 65 X D...