5-8
BE1-51/27R - Tests And Adjustments
NOTE
Due to delays inherent in the test equipment, the time delay for the following test may
appear to exceed these limits.
NOTE
For relays having two-phase and neutral, three-phase, or three-phase-and-neutral
sensing (sensing inputs types B, C, E, F, R, S, U, W, Y, or Z) it is not necessary to repeat
this test for the remaining phases.
For relays having two-phase-and-neutral, or three-phase-and-neutral sensing (sensing
input types E, F, U, W, Y, or Z) perform Steps 11 through 20.
For relays having single-phase or three-phase sensing (sensing input types B, C, M, N,
R, or S) with instantaneous overcurrent option 1-1 or 1-2: Proceed to the instantaneous
overcurrent test. All other relays proceed to the voltage restraint test.
Step 8.
Remove input current and (if present) reset the relay front panel targets.
Step 9.
On the appropriate time overcurrent curve chart (Figures 1-2 through 1-70), locate the line
representing 5 times the tap value (from Step 5) where it intersects the particular curve
representing the front panel TIME DIAL setting of 20 (from Step 4). The resulting time delay value
in seconds should be within ±5% of the timer reading [from step 7(2)].
Step 10. Adjust the front panel TIME DIAL to 40, 60, and 99, each time repeating Steps 6 through 9.
Step 11. Remove the power and reconnect the test output to the neutral current sensing input of the relay
as shown in Figures 5-3 and 5-5 (terminals 17 and 18).
Step 12. Set the front panel TAP (NEUTRAL) selector to B.
Step 13. Rotate the front panel CAL (NEUTRAL) control fully CW.
Step 14. Rotate the front panel TIME DIAL (NEUTRAL) to 20.
Step 15. Ensure that all relay targets have been reset.
Step 16. Adjust the test set for an overcurrent threshold of precisely 5 times the front panel TAP
(NEUTRAL) selector B setting as measured by the ammeter.
Step 17. Apply input current to the relay and initiate the test setup timer.
RESULTS: Observe that the appropriate front panel TIMING (NEUTRAL) indicator illuminates.
Step 18. When the time delay ends, the timed output relay is energized.
RESULTS:
(1)
The front panel TIMING (NEUTRAL) indicator extinguishes.
(2)
The test setup timer stops. (Record count for use in Step 20.)
(3)
If target Type A or B is present:
(a)
Front panel FUNCTION-TIME target (if present) trips.
(b)
Appropriate front panel ELEMENT target A, B, or C (if present)
trips.
Step 19. Remove input current and (if present) reset the relay front panel targets.
Содержание BE1-51/27R
Страница 14: ...BE1 51 27R General Information 1 9 Figure 1 1 Style Number Identification Chart...
Страница 36: ...BE1 51 27R General Information 1 31 Figure 1 38 Timing Type E7 BS 142 Extremely Inverse Drawing No 99 1097...
Страница 54: ...2 2 BE1 51 27R Human Machine Interface Controls And Indicators Figure 2 1 Location of Controls and Indicators...
Страница 59: ...3 2 BE1 51 27R Functional Description Figure 3 1 Functional Block Diagram...
Страница 69: ...BE1 51 27R Installation 4 7 Figure 4 8 Typical Internal Diagram Sensing Input Type M or N...
Страница 76: ...4 14 BE1 51 27R Installation Figure 4 14 Relay Signals and Current Pickup Example For 3 Phase Fault XE 0 65 X D...