2-4
BE1-51/27R - Human Machine Interface (Controls And Indicators)
Table 2-2. Sensing Input Ranges
TAP Range
Plate or
Pickup
TAP Selector
Current Sensing Terminals
A
B
C
D
E
F
G
H
I
J
A
B
C
N
Range 1, Single-Phase †
HIGH
2.25
3.00
4.50
5.25
6.75
7.50
9.00
9.75
11.2
5
12.0
0
8,7
-----
-----
-----
LOW
0.75
1.00
1.50
1.75
2.25
2.50
3.00
3.25
3.75
4.00
9,7
-----
-----
-----
Range 1, Three-Phase †
HIGH
2.25
3.00
4.50
5.25
6.75
7.50
9.00
9.75
11.2
5
12.0
0
8,7
14,15
17,18
-----
LOW
0.75
1.00
1.50
1.75
2.25
2.50
3.00
3.25
3.75
4.00
9,7
13,15
16,18
-----
Range 1, Two-Phase-and-Neutral †
HIGH
2.25
3.00
4.50
5.25
6.75
7.50
9.00
9.75
11.2
5
12.0
0
8,7
-----
14,15
17,18
LOW
0.75
1.00
1.50
1.75
2.25
2.50
3.00
3.25
3.75
4.00
9,7
-----
13,15
16,18
Range 2, Three-Phase-and-Neutral
Phase or
Neutral
0.75
1.00
1.50
1.75
2.25
2.50
3.00
3.25
3.75
4.00
8,9
13,14
15,16
17,18
Range 3, Three-Phase-and-Neutral
Phase
2.25
3.00
4.50
5.25
6.75
7.50
9.00
9.75
11.2
5
12.0
0
8,9
13,14
15,16
-----
Neutral
0.75
1.00
1.50
1.75
2.25
2.50
3.00
3.25
3.75
4.00
-----
-----
-----
17,18
Range 4, Three-Phase-and-Neutral
Phase
0.75
1.00
1.50
1.75
2.25
2.50
3.00
3.25
3.75
4.00
8,9
13,14
15,16
-----
Neutral
2.25
3.00
4.50
5.25
6.75
7.50
9.00
9.75
11.2
5
12.0
0
-----
-----
-----
17,18
Range 5, Three-Phase-and-Neutral
Phase
or
Neutral
2.25
3.00
4.50
5.25
6.75
7.50
9.00
9.75
11.2
5
12.0
0
8,9
13,14
15,16
17,18
Range 6, Three-Phase-and-Neutral
Phase
or
Neutral
0.15
0.20
0.30
0.35
0.45
0.50
0.60
0.65
0.75
0.80
8,9
13,14
15,16
17,18
Range 7, Three-Phase-and-Neutral
Phase
0.45
0.60
0.90
1.05
1.35
1.50
1.80
1.95
2.25
2.40
8,9
13,14
15,16
-----
Neutral
0.15
0.20
0.30
0.35
0.45
0.50
0.60
0.65
0.75
0.80
-----
-----
-----
17,18
Range 8, Three-Phase-and-Neutral
Phase
or
Neutral
0.45
0.60
0.90
1.05
1.35
1.50
1.80
1.95
2.25
2.40
8,9
13,14
15,16
17,18
Range 9 (All Other Sensing Types)
HIGH
0.45
0.60
0.90
1.05
1.35
1.50
1.80
1.95
2.25
2.40
8,7
-----
-----
-----
LOW
0.15
0.20
0.30
0.35
0.45
0.50
0.60
0.65
0.75
0.80
9,7
-----
-----
-----
NOTE:
†
For relays with sensing input range 1, connect the system wiring to the current sensing terminals
for the desired range (HIGH or LOW).
Содержание BE1-51/27R
Страница 14: ...BE1 51 27R General Information 1 9 Figure 1 1 Style Number Identification Chart...
Страница 36: ...BE1 51 27R General Information 1 31 Figure 1 38 Timing Type E7 BS 142 Extremely Inverse Drawing No 99 1097...
Страница 54: ...2 2 BE1 51 27R Human Machine Interface Controls And Indicators Figure 2 1 Location of Controls and Indicators...
Страница 59: ...3 2 BE1 51 27R Functional Description Figure 3 1 Functional Block Diagram...
Страница 69: ...BE1 51 27R Installation 4 7 Figure 4 8 Typical Internal Diagram Sensing Input Type M or N...
Страница 76: ...4 14 BE1 51 27R Installation Figure 4 14 Relay Signals and Current Pickup Example For 3 Phase Fault XE 0 65 X D...