background image

2

The references listed on Page 22 provide more
background on this subject. These documents
also contain Bibliographies for further study.

Ground Fault Protection

The following information and examples cover
three impedance levels of grounding: low,
medium, and high. A low impedance grounded
generator refers to a generator that has zero or
minimal impedance applied at the Wye neutral
point so that, during a ground fault at the genera-
tor HV terminals, ground current from the genera-
tor is approximately equal to 3 phase fault
current. A medium impedance grounded genera-
tor refers to a generator that has substantial im-
pedance applied at the wye neutral point so that,
during a ground fault, a reduced but readily de-
tectable level of ground current, typically on the
order of 100-500A, flows. A high impedance
grounded generator refers to a generator with a
large grounding impedance so that, during a
ground fault, a nearly undetectable level of fault
current flows, necessitating ground fault monitor-
ing with voltage based (e.g., 3rd harmonic volt-
age monitoring and fundamental frequency neu-
tral voltage shift monitoring) relays. The location
of the grounding, generator neutral(s) or trans-
former, also influences the protection approach.

The location of the ground fault within the gen-
erator winding, as well as the grounding imped-
ance, determines the level of fault current.
Assuming that the generated voltage along each
segment of the winding is uniform, the prefault
line-ground voltage level is proportional to the
percent of winding between the fault location and
the generator neutral, V

FG

 in Fig. 1. Assuming an

impedance grounded generator where  (Z

0, SOURCE

and Z

N

)>>Z

WINDING

, the current level is directly

proportional to the distance of the point from the
generator neutral [Fig. 1(a)], so a fault 10% from
neutral produces 10% of the current that flows
for a fault on the generator terminals. While the
current level drops towards zero as the neutral is
approached, the insulation stress also drops,
tending to reduce the probability of a fault near
the neutral. If a generator grounding impedance
is low relative to the generator winding imped-
ance or the system ground impedance is low, the
fault current decay will be non-linear. For 

I

1

 in

Fig. 1, lower fault voltage is offset by lower

generator winding resistance. An example is
shown in Fig. 1(b).

The generator differential relay (87G) may be
sensitive enough to detect winding ground faults
with low-impedance grounding per Fig. 2. This
would be the case if a solid generator-terminal
fault produces approximately 100% of rated
current. The minimum pickup setting of the
differential relays (e.g., Basler BE1-CDS220 or
BE1-87G, Table 2) should be adjusted to sense
faults on as much of the winding as possible.
However, settings below 10% of full load current
(e.g., 0.4A for 4A full load current) carry in-
creased risk of misoperation due to transient CT
saturation during external faults or during step-up
transformer energization. Lower pickup settings
are recommended only with high-quality CTs
(e.g., C400) and a good CT match (e.g., identical
accuracy class and equal burden).

FIGURE 1. EFFECTS OF FAULT LOCATION WITHIN
GENERATOR ON CURRENT LEVEL.

If 87G relaying is provided per Fig. 2, relay 51N
(e.g., Basler relays per Table 2) backs up the
87G, as well as external relays. If an 87G is not
provided or is not sufficiently sensitive for ground

Содержание BE1-1051

Страница 1: ...GeneratorProtection ApplicationGuide...

Страница 2: ...ign of protective relaying systems He worked for Consolidated Edison Company for ten years as a System Engineer He has served as a private consultant since 1982 Updates and additions performed by vari...

Страница 3: ...it is rather expected that a 500kW 480V standby reciprocating engine will have less protection than a 400MW base load steam turbine unit One possible common dividing point is that the extra CTs neede...

Страница 4: ...ral VFG in Fig 1 Assuming an impedancegroundedgeneratorwhere Z0 SOURCE and ZN ZWINDING the current level is directly proportional to the distance of the point from the generator neutral Fig 1 a so a f...

Страница 5: ...rcuit or setting the relay fairly insensitively FIGURE 2 GROUND FAULT RELAYING GENERATOR LOW IMPEDANCE GROUNDING The neutral CT should be selected to produce a secondary current of at least 5A for a s...

Страница 6: ...gh rejection of fundamental frequency voltage FIGURE 6 GROUND FAULT NEAR GENERATOR NEUTRAL REDUCES THIRD HARMONIC VOLTAGE IN GENERATOR NEUTRAL DROPPING OUT 27 3N The 27 3N performs a valuable monitori...

Страница 7: ...ult as seen by the generator neutral shift sensing relay 59N leading to a generator trip Alternatively assume that the VT corner e g phase A has been grounded If phase B or C fault to ground the fault...

Страница 8: ...2 100 5 from the neutral When feeder cables are connected to the gen erator bus the additional capacitance dictates a much lower level of grounding resistance than achieved with a unit connected case...

Страница 9: ...hout pre loading For example assuming a pre fault 1pu rated load at 30 degree lag at one second the 3 phase fault value would be 2 4 times rated rather than 1 75 timesrated 1 30 1 75 90 2 4 69 Under t...

Страница 10: ...edapproach inhibits operation until the voltage drops below a preset voltage It should be set to function below about 80 of rated voltage with a current pickup of about 50 of generator rated Since the...

Страница 11: ...imes tap CDS220 or 0 4A 87G is representa tive of a recommended setting for a moderate mismatch in CT quality and burden Fig 13 also shows 51V relays to back up the 87G and external relays and breaker...

Страница 12: ...nchroniz ing when the generator is initially slower than the system Since motoring can occur during a large reactive power flow the real power component needs to be measured at low power factors The B...

Страница 13: ...y a mho circle centered about the X axis offset from the R axis by X d 2 Two zones sometimes are used a high speed zone and a time delayed zone FIG 19 LOSS OF EXCITATION USING IMPEDANCE RELAY With com...

Страница 14: ...r during a fault To prevent a 60FL from being declared during loss of station power it may be necessary to allow a 3 phase 60F to be declared only when some low level of load current exists FIGURE 22...

Страница 15: ...ach set point may be set to recognize either over frequency or underfrequency Multiple frequency set points are available in the BE1 81O U BE1 GPS100 BE1 951 and BE1 1051 Another common need for frequ...

Страница 16: ...ld be employed where protection independent of the plant is desired In this case the 67 relays would be placed in the switchyard rather than in the control room While directional overcurrent relay 67...

Страница 17: ...reaker depending on the type of fault that is detected For instance if the generator is protected by a 51V and an 87G and only the 51V trips it may be assumed that the fault is external to the generat...

Страница 18: ...EXAMPLE OF BARE MINIMUM PROTECTION LOW IMPEDANCE GROUNDING Fig 30 shows the suggested minimum protection with low resistance grounding It includes differential protection which provides fast selectiv...

Страница 19: ...ssive generator reactive absorption Ther mal relay 49 protects against stator overheating due to protracted heavy reactive power demands and loss of generator cooling Even if the excitation system is...

Страница 20: ...voltage balancerelay 60 field ground relay 64F frequency relay 81 and the 27 50 62 relay combination for inadvertent energization protection Relay 51GN provides a second means of detecting stator gro...

Страница 21: ...ures 34 through 37 show the BE1 GPS100 and BE1 CDS220 applied to generator protection Due to logic complexity full details are not shown Details of these applica tions may be found in the respective i...

Страница 22: ...20 FIGURE 35 BE1 GPS100 APPLIED TO HIGH IMPEDANCE GROUNDED GENERATOR HI_Z_GND PREPROGRAMMED LOGIC SEE INSTRUCTION MANUAL FOR LOGIC DETAILS...

Страница 23: ...FIGURE 36 BE1 CDS220 APPLIED TO GENERATOR FOR 87 PHASE 87 NEUTRAL AND 51 PHASE NEUTRAL GROUND AND NEGATIVE SEQUENCE 21...

Страница 24: ...s typical settings for use as a starting point in the setting determi nation procedure The proper settings are heavily influenced by the specifics of each application Typical settings are also used as...

Страница 25: ...urrent 49 20 StatorTemperature RTD Lower 95 C upper 105 C 50 87 12 Differentialviaflux PU 10 INOM or less if 1A relay may be used summationCTs 50 27 IE 24 InadvertentEnergization 50 0 5A 10 INOM Overc...

Страница 26: ...75 100 INOM GEN Definite Time 0 1 0 25 sec InadvertentEnergization Inst 200 INOM GEN 81 21 Over underfrequency Generator protection 57 62Hz 0 5s Island detection 59 61Hz 0 1s 87G 13 GeneratorPhase BE1...

Страница 27: ...9 59 X X X X X X 59N 27 3N 59N 59P 4 4 4 60FL 60 X X X 67IE 67 X X 81 81O U 81O U X X X X X 87G 87G X 87N 67N 87UD 87T X 1 50 51G Indicates a relay that monitors a ground CT source 2 50 51N Indicates...

Страница 28: ...54 2341 Fax 1 618 654 2351 BaslerElectricInternational P A E Les Pins 67319 Wasselonne Cedex FRANCE Phone 33 3 88 87 1010 Fax 33 3 88 87 0808 If you have any questions or need additionalinformation pl...

Отзывы: