background image

4

in Fig. 5, a ground fault at the generator high
voltage bushings elevates the sound phase line to
ground voltages to a nominal 173% of normal line
to neutral voltages. Also, the neutral to ground
voltage will rise to the normal phase-ground
voltage levels. The closer the ground fault is to
the generator neutral, the less the neutral to
ground voltage will be. One method to sense this
neutral shift is with the 59N relay (Fig. 4) monitor-
ing the generator neutral. The 59N will sense and
protect the generator for ground faults over about
95% of the generator winding. The selected 59N
(Basler relays per Table 2) relay should be
selected so as to not respond to third harmonic
voltage produced during normal operation. The
59N will not operate for faults near the generator
neutral because of the reduced neutral shift during
this type of fault.

FIGURE 5. NEUTRAL SHIFT DURING GROUND FAULT
ON HIGH IMPEDANCE GROUNDED SYSTEM.

Faults near the generator neutral may be sensed
with the 27-3N. When high impedance grounding
is in use, a detectable level of third harmonic
voltage will usually exist at the generator neutral,
typically 1-5% of generator line to neutral funda-
mental voltage. The level of third harmonic is
dependent on generator design and may be very
low in some generators (a 2/3 pitch machine will
experience a notably reduced third harmonic
voltage). The level of harmonic voltage will likely
decrease at lower excitation levels and lower load
levels. During ground faults near the generator
neutral, the third harmonic voltage in the generator
neutral is shorted to ground, causing the 27-3N to
drop out (Fig. 6). It is important that the 27-3N
have high rejection of fundamental frequency
voltage.

FIGURE 6. GROUND FAULT NEAR GENERATOR
NEUTRAL REDUCES THIRD-HARMONIC VOLTAGE IN
GENERATOR NEUTRAL, DROPPING OUT 27-3N.

The 27-3N performs a valuable monitoring
function aside from its fault detection function; if
the grounding system is shorted or an open
occurs, the 27-3N drops out.

The 59P phase overvoltage relay in Fig. 4
supervises the 27-3N relay, so that the 86
lockout relay can be reset when the generator is
out of service; otherwise, the field could not be
applied. Once the field is applied and the 59P
operates, the 27-3N protection is enabled. The
59P relay should be set for about 90% of rated
voltage. An “a” contact of the unit breaker can be
used instead of the 59P relay to supervise 27-3N
tripping. Blocking the 27-3N until some level of
forward power exists also has been done.
However, use of the 59P relay allows the 27-3N
to provide protection prior to synchronization
(i.e., putting the unit on line), once the field has
been applied.

In order to provide 100% stator winding cover-
age, the undervoltage (27-3N) and overvoltage
(59N) settings should overlap. For example, if a
generator-terminal fault produces 240V, 60 Hz
across the neutral voltage relay (59N), a 1V
pickup setting (a fairly sensitive setting) would
allow all but the last (1/240)*100 = 0.416% of the
winding to be covered by the overvoltage
function. If 20V third harmonic is developed
across the relay prior to a fault, a 1V third-
harmonic drop-out setting would provide dropout
for a fault up to (1/20)*100= 5% from the neutral.
Setting the 59N pickup too low or the 27N
dropout too low may result in operation of the
ground detection system during normal operating
conditions. The third harmonic dropout level may
be hardest to properly set, since its level is
dependent on machine design and generator
excitation and load levels. It may be advisable to

Содержание BE1-1051

Страница 1: ...GeneratorProtection ApplicationGuide...

Страница 2: ...ign of protective relaying systems He worked for Consolidated Edison Company for ten years as a System Engineer He has served as a private consultant since 1982 Updates and additions performed by vari...

Страница 3: ...it is rather expected that a 500kW 480V standby reciprocating engine will have less protection than a 400MW base load steam turbine unit One possible common dividing point is that the extra CTs neede...

Страница 4: ...ral VFG in Fig 1 Assuming an impedancegroundedgeneratorwhere Z0 SOURCE and ZN ZWINDING the current level is directly proportional to the distance of the point from the generator neutral Fig 1 a so a f...

Страница 5: ...rcuit or setting the relay fairly insensitively FIGURE 2 GROUND FAULT RELAYING GENERATOR LOW IMPEDANCE GROUNDING The neutral CT should be selected to produce a secondary current of at least 5A for a s...

Страница 6: ...gh rejection of fundamental frequency voltage FIGURE 6 GROUND FAULT NEAR GENERATOR NEUTRAL REDUCES THIRD HARMONIC VOLTAGE IN GENERATOR NEUTRAL DROPPING OUT 27 3N The 27 3N performs a valuable monitori...

Страница 7: ...ult as seen by the generator neutral shift sensing relay 59N leading to a generator trip Alternatively assume that the VT corner e g phase A has been grounded If phase B or C fault to ground the fault...

Страница 8: ...2 100 5 from the neutral When feeder cables are connected to the gen erator bus the additional capacitance dictates a much lower level of grounding resistance than achieved with a unit connected case...

Страница 9: ...hout pre loading For example assuming a pre fault 1pu rated load at 30 degree lag at one second the 3 phase fault value would be 2 4 times rated rather than 1 75 timesrated 1 30 1 75 90 2 4 69 Under t...

Страница 10: ...edapproach inhibits operation until the voltage drops below a preset voltage It should be set to function below about 80 of rated voltage with a current pickup of about 50 of generator rated Since the...

Страница 11: ...imes tap CDS220 or 0 4A 87G is representa tive of a recommended setting for a moderate mismatch in CT quality and burden Fig 13 also shows 51V relays to back up the 87G and external relays and breaker...

Страница 12: ...nchroniz ing when the generator is initially slower than the system Since motoring can occur during a large reactive power flow the real power component needs to be measured at low power factors The B...

Страница 13: ...y a mho circle centered about the X axis offset from the R axis by X d 2 Two zones sometimes are used a high speed zone and a time delayed zone FIG 19 LOSS OF EXCITATION USING IMPEDANCE RELAY With com...

Страница 14: ...r during a fault To prevent a 60FL from being declared during loss of station power it may be necessary to allow a 3 phase 60F to be declared only when some low level of load current exists FIGURE 22...

Страница 15: ...ach set point may be set to recognize either over frequency or underfrequency Multiple frequency set points are available in the BE1 81O U BE1 GPS100 BE1 951 and BE1 1051 Another common need for frequ...

Страница 16: ...ld be employed where protection independent of the plant is desired In this case the 67 relays would be placed in the switchyard rather than in the control room While directional overcurrent relay 67...

Страница 17: ...reaker depending on the type of fault that is detected For instance if the generator is protected by a 51V and an 87G and only the 51V trips it may be assumed that the fault is external to the generat...

Страница 18: ...EXAMPLE OF BARE MINIMUM PROTECTION LOW IMPEDANCE GROUNDING Fig 30 shows the suggested minimum protection with low resistance grounding It includes differential protection which provides fast selectiv...

Страница 19: ...ssive generator reactive absorption Ther mal relay 49 protects against stator overheating due to protracted heavy reactive power demands and loss of generator cooling Even if the excitation system is...

Страница 20: ...voltage balancerelay 60 field ground relay 64F frequency relay 81 and the 27 50 62 relay combination for inadvertent energization protection Relay 51GN provides a second means of detecting stator gro...

Страница 21: ...ures 34 through 37 show the BE1 GPS100 and BE1 CDS220 applied to generator protection Due to logic complexity full details are not shown Details of these applica tions may be found in the respective i...

Страница 22: ...20 FIGURE 35 BE1 GPS100 APPLIED TO HIGH IMPEDANCE GROUNDED GENERATOR HI_Z_GND PREPROGRAMMED LOGIC SEE INSTRUCTION MANUAL FOR LOGIC DETAILS...

Страница 23: ...FIGURE 36 BE1 CDS220 APPLIED TO GENERATOR FOR 87 PHASE 87 NEUTRAL AND 51 PHASE NEUTRAL GROUND AND NEGATIVE SEQUENCE 21...

Страница 24: ...s typical settings for use as a starting point in the setting determi nation procedure The proper settings are heavily influenced by the specifics of each application Typical settings are also used as...

Страница 25: ...urrent 49 20 StatorTemperature RTD Lower 95 C upper 105 C 50 87 12 Differentialviaflux PU 10 INOM or less if 1A relay may be used summationCTs 50 27 IE 24 InadvertentEnergization 50 0 5A 10 INOM Overc...

Страница 26: ...75 100 INOM GEN Definite Time 0 1 0 25 sec InadvertentEnergization Inst 200 INOM GEN 81 21 Over underfrequency Generator protection 57 62Hz 0 5s Island detection 59 61Hz 0 1s 87G 13 GeneratorPhase BE1...

Страница 27: ...9 59 X X X X X X 59N 27 3N 59N 59P 4 4 4 60FL 60 X X X 67IE 67 X X 81 81O U 81O U X X X X X 87G 87G X 87N 67N 87UD 87T X 1 50 51G Indicates a relay that monitors a ground CT source 2 50 51N Indicates...

Страница 28: ...54 2341 Fax 1 618 654 2351 BaslerElectricInternational P A E Les Pins 67319 Wasselonne Cedex FRANCE Phone 33 3 88 87 1010 Fax 33 3 88 87 0808 If you have any questions or need additionalinformation pl...

Отзывы: