background image

fault occur. This is an unlikely event, because
other fault sensing relaying tends to clear faults
faster, even if primary protection fails.

Fig. 26 shows the 46 relay connection. CTs on
either side of the generator can be used, since
the relay protects for events external to the
generator. The Basler BE1-46N alarm unit will
alert the operator to the existence of a dangerous
condition.

FIGURE 26. NEGATIVE-SEQUENCE CURRENT RELAY
(46) PROTECTS AGAINST ROTOR OVERHEATING
DUE TO A SERIES UNBALANCE OR PROTRACTED
EXTERNAL FAULT. NEGATIVE SEQUENCE VOLTAGE
RELAY (47) (LESS COMMONLY APPLIED) ALSO
RESPONDS.

Negative sequence voltage (47) protection, while
not as commonly used, is an available means to
sense system imbalance as well as, in some
situations, a misconnection of the generator to a
system to which it is being paralleled.

Out of Step Protection

When a generator pulls out of synchronism with
the system, current will rise relatively slowly
compared to the instantaneous change in current
associated with a fault. The out-of-step relay
uses impedance techniques to sense this
condition. The relay will see an apparent load
impedance swing as impedance moves from
Zone 1 to Zone 2 (Fig. 27). The time it takes for
the load impedance to traverse from Zone 1 to
Zone 2 is used to decide if an out of step

FIGURE 27. OUT OF STEP RELAYING (78)

condition is occurring. A moving impedance is
identified as a swing rather than a fault, so
appropriate fault detection relaying may be
blocked.

Selective Tripping and Sequential Tripping

It is a practice at some generators to selectively
trip the prime mover, the field, and the generator
breaker, depending on the type of fault that is
detected. For instance, if the generator is
protected by a 51V and an 87G, and only the
51V trips, it may be assumed that the fault is
external to the generator and, hence, the 51V
only trips the generator breaker and rapidly pulls
back the excitation governor and prime mover
set points. However, if there is no 87G, the 51V
trips the entire unit. Associated with this concept
is sequential tripping used for orderly shutdown.
To prevent overspeeding a generator during
shutdown, it is sometimes the practice first to
trip the prime mover and trip the main breaker
and field only after a reverse power relay verifies
the prime mover has stopped providing torque to
the generator.

Synchronism Check and Auto Synchronizing

Before connecting a generator to the power
system, it is important that the generator and
system frequency, voltage magnitude, and
phase angle be in alignment, referred to as
synchronism checking (25). Typical parameters
are shown in Fig. 28. Typical applications call for
no more than 6RPM error, 2% voltage magnitude
difference, and no more than 10° phase angle
error before closing the breaker. The Basler
BE1-951, BE1-GPS, and BE1-25 all can perform
the sync check function.

Auto synchronizing (25A) refers to a system to
automatically bring a generator into synchronism
with the power system. It involves sending
voltage and speed raise and lower commands to
the voltage regulator and prime mover governor.
When the system is in synchronism, the
autosync relay is sometimes designed to send a
close command in advance of the zero phase
angle error point to compensate for breaker close
delays. The 25 relay, which usually is set to
supervise the 25A and manual sync function,
usually is set less tight than the 25A so as to
coordinate with the actions of the 25A.

15

Содержание BE1-1051

Страница 1: ...GeneratorProtection ApplicationGuide...

Страница 2: ...ign of protective relaying systems He worked for Consolidated Edison Company for ten years as a System Engineer He has served as a private consultant since 1982 Updates and additions performed by vari...

Страница 3: ...it is rather expected that a 500kW 480V standby reciprocating engine will have less protection than a 400MW base load steam turbine unit One possible common dividing point is that the extra CTs neede...

Страница 4: ...ral VFG in Fig 1 Assuming an impedancegroundedgeneratorwhere Z0 SOURCE and ZN ZWINDING the current level is directly proportional to the distance of the point from the generator neutral Fig 1 a so a f...

Страница 5: ...rcuit or setting the relay fairly insensitively FIGURE 2 GROUND FAULT RELAYING GENERATOR LOW IMPEDANCE GROUNDING The neutral CT should be selected to produce a secondary current of at least 5A for a s...

Страница 6: ...gh rejection of fundamental frequency voltage FIGURE 6 GROUND FAULT NEAR GENERATOR NEUTRAL REDUCES THIRD HARMONIC VOLTAGE IN GENERATOR NEUTRAL DROPPING OUT 27 3N The 27 3N performs a valuable monitori...

Страница 7: ...ult as seen by the generator neutral shift sensing relay 59N leading to a generator trip Alternatively assume that the VT corner e g phase A has been grounded If phase B or C fault to ground the fault...

Страница 8: ...2 100 5 from the neutral When feeder cables are connected to the gen erator bus the additional capacitance dictates a much lower level of grounding resistance than achieved with a unit connected case...

Страница 9: ...hout pre loading For example assuming a pre fault 1pu rated load at 30 degree lag at one second the 3 phase fault value would be 2 4 times rated rather than 1 75 timesrated 1 30 1 75 90 2 4 69 Under t...

Страница 10: ...edapproach inhibits operation until the voltage drops below a preset voltage It should be set to function below about 80 of rated voltage with a current pickup of about 50 of generator rated Since the...

Страница 11: ...imes tap CDS220 or 0 4A 87G is representa tive of a recommended setting for a moderate mismatch in CT quality and burden Fig 13 also shows 51V relays to back up the 87G and external relays and breaker...

Страница 12: ...nchroniz ing when the generator is initially slower than the system Since motoring can occur during a large reactive power flow the real power component needs to be measured at low power factors The B...

Страница 13: ...y a mho circle centered about the X axis offset from the R axis by X d 2 Two zones sometimes are used a high speed zone and a time delayed zone FIG 19 LOSS OF EXCITATION USING IMPEDANCE RELAY With com...

Страница 14: ...r during a fault To prevent a 60FL from being declared during loss of station power it may be necessary to allow a 3 phase 60F to be declared only when some low level of load current exists FIGURE 22...

Страница 15: ...ach set point may be set to recognize either over frequency or underfrequency Multiple frequency set points are available in the BE1 81O U BE1 GPS100 BE1 951 and BE1 1051 Another common need for frequ...

Страница 16: ...ld be employed where protection independent of the plant is desired In this case the 67 relays would be placed in the switchyard rather than in the control room While directional overcurrent relay 67...

Страница 17: ...reaker depending on the type of fault that is detected For instance if the generator is protected by a 51V and an 87G and only the 51V trips it may be assumed that the fault is external to the generat...

Страница 18: ...EXAMPLE OF BARE MINIMUM PROTECTION LOW IMPEDANCE GROUNDING Fig 30 shows the suggested minimum protection with low resistance grounding It includes differential protection which provides fast selectiv...

Страница 19: ...ssive generator reactive absorption Ther mal relay 49 protects against stator overheating due to protracted heavy reactive power demands and loss of generator cooling Even if the excitation system is...

Страница 20: ...voltage balancerelay 60 field ground relay 64F frequency relay 81 and the 27 50 62 relay combination for inadvertent energization protection Relay 51GN provides a second means of detecting stator gro...

Страница 21: ...ures 34 through 37 show the BE1 GPS100 and BE1 CDS220 applied to generator protection Due to logic complexity full details are not shown Details of these applica tions may be found in the respective i...

Страница 22: ...20 FIGURE 35 BE1 GPS100 APPLIED TO HIGH IMPEDANCE GROUNDED GENERATOR HI_Z_GND PREPROGRAMMED LOGIC SEE INSTRUCTION MANUAL FOR LOGIC DETAILS...

Страница 23: ...FIGURE 36 BE1 CDS220 APPLIED TO GENERATOR FOR 87 PHASE 87 NEUTRAL AND 51 PHASE NEUTRAL GROUND AND NEGATIVE SEQUENCE 21...

Страница 24: ...s typical settings for use as a starting point in the setting determi nation procedure The proper settings are heavily influenced by the specifics of each application Typical settings are also used as...

Страница 25: ...urrent 49 20 StatorTemperature RTD Lower 95 C upper 105 C 50 87 12 Differentialviaflux PU 10 INOM or less if 1A relay may be used summationCTs 50 27 IE 24 InadvertentEnergization 50 0 5A 10 INOM Overc...

Страница 26: ...75 100 INOM GEN Definite Time 0 1 0 25 sec InadvertentEnergization Inst 200 INOM GEN 81 21 Over underfrequency Generator protection 57 62Hz 0 5s Island detection 59 61Hz 0 1s 87G 13 GeneratorPhase BE1...

Страница 27: ...9 59 X X X X X X 59N 27 3N 59N 59P 4 4 4 60FL 60 X X X 67IE 67 X X 81 81O U 81O U X X X X X 87G 87G X 87N 67N 87UD 87T X 1 50 51G Indicates a relay that monitors a ground CT source 2 50 51N Indicates...

Страница 28: ...54 2341 Fax 1 618 654 2351 BaslerElectricInternational P A E Les Pins 67319 Wasselonne Cedex FRANCE Phone 33 3 88 87 1010 Fax 33 3 88 87 0808 If you have any questions or need additionalinformation pl...

Отзывы: