background image

6

set lower if the relay filters harmonic currents
and responds only to fundamental currents.)
Assuming a maximum fault current of 8A primary
in the neutral and a relay set to pick up at 1A
primary, 88% of the stator winding is covered.
As with the 59N relay, the 51GN delay will allow
it to override clearing of a high-side ground fault.
An instantaneous overcurrent element can also
be employed, set at about three times the time-
overcurrent element pickup, although it may not
coordinate with primary vt fuses that are con-
nected to the generator terminals.

Multiple generators, per Fig. 7, can be high-
resistance grounded, but the 59N relays will not
be selective. A ground fault anywhere on the
generation bus or on the individual generators will
be seen by all 59N relays, and the tendency will
be for all generators to trip. The 51N relay, when
connected to a flux summation CT, will provide
selective tripping if at least three generators are
in service. In this case, the faulted generator
51N relay will then see more current than the
other 51N relays. The proper 51N will operate
before the others because of the inverse charac-
teristic of the relays. Use of the flux summation
CT is limited to those cases where the CT
window can accommodate the three cables.
Fault currents are relatively low, so care must be
exercised in selecting appropriate nominal relay
current level (e.g., 5A vs. 1A) and CT ratio. For
example, with a 30A fault level and a 50 to 5A
CT, a 1A nominal 51N with a pickup of 0.1A
might be used. With two generators, each
contributing 10A to a terminal fault in a third
generator, the faulted-generator 51N relay sees
2*10/(50/5) = 2A. Then the relay protects down
to (0.1/2)*100 = 5% from the neutral.

When feeder cables are connected to the gen-
erator bus, the additional capacitance dictates a
much lower level of grounding resistance than
achieved with a unit-connected case. A lower re-
sistance is required to minimize transient over-
voltages during an arcing fault.

FIGURE 7. 59N RELAY OPERATION WITH MULTIPLE
UNITS WILL NOT BE SELECTIVE; 51N RELAYS PRO-
VIDE SELECTIVE PROTECTION IF AT LEAST THREE
GENERATORS ARE IN SERVICE.

Ground differential (Fig. 8) is a good method to
sense ground faults on low and medium imped-
ance grounded units. It would more commonly be
seen on generators that have the CTs required
for phase differential relaying. In Fig. 8, the
protective function is labeled 87N, but the Basler
BE1-CDS220 or the BE1-67N is applied. The
BE1-CDS220 approach is more applicable to low
and medium impedance grounded generators
with ground faults as low as 50% of phase fault
current. The BE1-67N approach is more appli-
cable to medium impedance generators with low
ground fault current levels. The BE1-CDS220 is
limited in sensitivity to ground faults in excess of
10% of the phase CT tap setting, but the use of
the auxiliary CT in the BE1-67N approach allows
for amplification of the ground current in the
phase CTs, yielding increased sensitivity.
Whichever approach is used, an effort should be
made to select relay settings to trip for faults as
low as 10% of maximum ground fault current
levels. During external phase faults, considerable
87N operating current can occur when there is
dissimilar saturation of the phase CTs due to
high AC current or due to transient DC offset
effects, while the generator neutral current still
will be zero, assuming balanced conductor
impedances to the fault. One method to compen-
sate for transient CT saturation is to have
sufficient delay in the relay to ride through
external high-current two-phase-ground faults.

Содержание BE1-1051

Страница 1: ...GeneratorProtection ApplicationGuide...

Страница 2: ...ign of protective relaying systems He worked for Consolidated Edison Company for ten years as a System Engineer He has served as a private consultant since 1982 Updates and additions performed by vari...

Страница 3: ...it is rather expected that a 500kW 480V standby reciprocating engine will have less protection than a 400MW base load steam turbine unit One possible common dividing point is that the extra CTs neede...

Страница 4: ...ral VFG in Fig 1 Assuming an impedancegroundedgeneratorwhere Z0 SOURCE and ZN ZWINDING the current level is directly proportional to the distance of the point from the generator neutral Fig 1 a so a f...

Страница 5: ...rcuit or setting the relay fairly insensitively FIGURE 2 GROUND FAULT RELAYING GENERATOR LOW IMPEDANCE GROUNDING The neutral CT should be selected to produce a secondary current of at least 5A for a s...

Страница 6: ...gh rejection of fundamental frequency voltage FIGURE 6 GROUND FAULT NEAR GENERATOR NEUTRAL REDUCES THIRD HARMONIC VOLTAGE IN GENERATOR NEUTRAL DROPPING OUT 27 3N The 27 3N performs a valuable monitori...

Страница 7: ...ult as seen by the generator neutral shift sensing relay 59N leading to a generator trip Alternatively assume that the VT corner e g phase A has been grounded If phase B or C fault to ground the fault...

Страница 8: ...2 100 5 from the neutral When feeder cables are connected to the gen erator bus the additional capacitance dictates a much lower level of grounding resistance than achieved with a unit connected case...

Страница 9: ...hout pre loading For example assuming a pre fault 1pu rated load at 30 degree lag at one second the 3 phase fault value would be 2 4 times rated rather than 1 75 timesrated 1 30 1 75 90 2 4 69 Under t...

Страница 10: ...edapproach inhibits operation until the voltage drops below a preset voltage It should be set to function below about 80 of rated voltage with a current pickup of about 50 of generator rated Since the...

Страница 11: ...imes tap CDS220 or 0 4A 87G is representa tive of a recommended setting for a moderate mismatch in CT quality and burden Fig 13 also shows 51V relays to back up the 87G and external relays and breaker...

Страница 12: ...nchroniz ing when the generator is initially slower than the system Since motoring can occur during a large reactive power flow the real power component needs to be measured at low power factors The B...

Страница 13: ...y a mho circle centered about the X axis offset from the R axis by X d 2 Two zones sometimes are used a high speed zone and a time delayed zone FIG 19 LOSS OF EXCITATION USING IMPEDANCE RELAY With com...

Страница 14: ...r during a fault To prevent a 60FL from being declared during loss of station power it may be necessary to allow a 3 phase 60F to be declared only when some low level of load current exists FIGURE 22...

Страница 15: ...ach set point may be set to recognize either over frequency or underfrequency Multiple frequency set points are available in the BE1 81O U BE1 GPS100 BE1 951 and BE1 1051 Another common need for frequ...

Страница 16: ...ld be employed where protection independent of the plant is desired In this case the 67 relays would be placed in the switchyard rather than in the control room While directional overcurrent relay 67...

Страница 17: ...reaker depending on the type of fault that is detected For instance if the generator is protected by a 51V and an 87G and only the 51V trips it may be assumed that the fault is external to the generat...

Страница 18: ...EXAMPLE OF BARE MINIMUM PROTECTION LOW IMPEDANCE GROUNDING Fig 30 shows the suggested minimum protection with low resistance grounding It includes differential protection which provides fast selectiv...

Страница 19: ...ssive generator reactive absorption Ther mal relay 49 protects against stator overheating due to protracted heavy reactive power demands and loss of generator cooling Even if the excitation system is...

Страница 20: ...voltage balancerelay 60 field ground relay 64F frequency relay 81 and the 27 50 62 relay combination for inadvertent energization protection Relay 51GN provides a second means of detecting stator gro...

Страница 21: ...ures 34 through 37 show the BE1 GPS100 and BE1 CDS220 applied to generator protection Due to logic complexity full details are not shown Details of these applica tions may be found in the respective i...

Страница 22: ...20 FIGURE 35 BE1 GPS100 APPLIED TO HIGH IMPEDANCE GROUNDED GENERATOR HI_Z_GND PREPROGRAMMED LOGIC SEE INSTRUCTION MANUAL FOR LOGIC DETAILS...

Страница 23: ...FIGURE 36 BE1 CDS220 APPLIED TO GENERATOR FOR 87 PHASE 87 NEUTRAL AND 51 PHASE NEUTRAL GROUND AND NEGATIVE SEQUENCE 21...

Страница 24: ...s typical settings for use as a starting point in the setting determi nation procedure The proper settings are heavily influenced by the specifics of each application Typical settings are also used as...

Страница 25: ...urrent 49 20 StatorTemperature RTD Lower 95 C upper 105 C 50 87 12 Differentialviaflux PU 10 INOM or less if 1A relay may be used summationCTs 50 27 IE 24 InadvertentEnergization 50 0 5A 10 INOM Overc...

Страница 26: ...75 100 INOM GEN Definite Time 0 1 0 25 sec InadvertentEnergization Inst 200 INOM GEN 81 21 Over underfrequency Generator protection 57 62Hz 0 5s Island detection 59 61Hz 0 1s 87G 13 GeneratorPhase BE1...

Страница 27: ...9 59 X X X X X X 59N 27 3N 59N 59P 4 4 4 60FL 60 X X X 67IE 67 X X 81 81O U 81O U X X X X X 87G 87G X 87N 67N 87UD 87T X 1 50 51G Indicates a relay that monitors a ground CT source 2 50 51N Indicates...

Страница 28: ...54 2341 Fax 1 618 654 2351 BaslerElectricInternational P A E Les Pins 67319 Wasselonne Cedex FRANCE Phone 33 3 88 87 1010 Fax 33 3 88 87 0808 If you have any questions or need additionalinformation pl...

Отзывы: