background image

8

Figure 9 shows the CTs on the neutral side of
the generator. This location allows the relay to
sense internal generator faults but does not
sense fault current coming into the generator
from the external system. Placing the CT on the
system side of the generator introduces a
problem of the relay not seeing a generator
internal fault when the main breaker is open and
when running the generator isolated from other
generation or the utility. If an external source
contributes more current than does the genera-
tor, using CTs on the generator terminals, rather
than neutral-side CTs, will increase 51 relay
sensitivity to internal faults due to higher current
contribution from the external source; however,
the generator is unprotected should a fault occur
with the breaker open or prior to synchronizing.

Voltage-restrained or voltage-controlled time-
overcurrent relays (51VR, 51VC) may be used as
shown in Fig. 11 to remove any concerns about
ability to operate before the generator current
drops too low. The voltage feature allows the
relays to be set below rated current. The Basler
BE1-951, BE1-1051, BE1-GPS100, and
BE1-51/27R voltage restrained approach causes
the pickup to decrease with decreasing voltage.
For example, the relay might be set for about
175% of generator rated current with rated
voltage applied; at 25% voltage the relay picks
up at 25% of the relay setting (1.75*0.25=0.44
times rated). The Basler BE1-951, BE1-GPS,
and BE1-51/27C voltage controlled approach
inhibits operation until the voltage drops below a
preset voltage. It should be set to function below
about 80% of rated voltage with a current pickup
of about 50% of generator rated. Since the
voltage-controlled type has a fixed pickup, it can
be more readily coordinated with external relays
than can the voltage-restrained type. The
voltage-controlled type is recommended since it
is easier to coordinate. However, the voltage-
restrained type will be less susceptible to
operation on swings or motor starting conditions
that depress the voltage below the voltage-
controlled undervoltage unit dropout point.

FIGURE 11. VOLTAGE-RESTRAINED OR VOLTAGE-
CONTROLLED TIME-OVERCURRENT PHASE FAULT
PROTECTION.

Fig. 12 eliminates concerns about the decay rate
of the generator current by using an instanta-
neous overcurrent relay (50) on a flux summation
CT, where the CT window can accommodate
cable from both sides of the generator. The relay
does not respond to generator load current nor to
external fault conditions. The instantaneous
overcurrent relay (50) acts as a phase differential
relay (87) and provides high-speed sensitive pro-
tection. This approach allows for high sensitivity.
For instance, it would be feasible to sense fault
currents as low as 1-5% of generator full load
current. It is common to use 50/5 CTs and to
use 1A nominal relaying. A low CT ratio intro-
duces critical saturation concerns (e.g., a 5,000A
primary fault may try to drive a 500A secondary
on a 50/5 CT). The CT burden must be low to
prevent saturation of the CT during internal faults
that may tend to highly overdrive the CT second-
ary.  The 51 relay shown in Fig. 12 is applied for

Содержание BE1-1051

Страница 1: ...GeneratorProtection ApplicationGuide...

Страница 2: ...ign of protective relaying systems He worked for Consolidated Edison Company for ten years as a System Engineer He has served as a private consultant since 1982 Updates and additions performed by vari...

Страница 3: ...it is rather expected that a 500kW 480V standby reciprocating engine will have less protection than a 400MW base load steam turbine unit One possible common dividing point is that the extra CTs neede...

Страница 4: ...ral VFG in Fig 1 Assuming an impedancegroundedgeneratorwhere Z0 SOURCE and ZN ZWINDING the current level is directly proportional to the distance of the point from the generator neutral Fig 1 a so a f...

Страница 5: ...rcuit or setting the relay fairly insensitively FIGURE 2 GROUND FAULT RELAYING GENERATOR LOW IMPEDANCE GROUNDING The neutral CT should be selected to produce a secondary current of at least 5A for a s...

Страница 6: ...gh rejection of fundamental frequency voltage FIGURE 6 GROUND FAULT NEAR GENERATOR NEUTRAL REDUCES THIRD HARMONIC VOLTAGE IN GENERATOR NEUTRAL DROPPING OUT 27 3N The 27 3N performs a valuable monitori...

Страница 7: ...ult as seen by the generator neutral shift sensing relay 59N leading to a generator trip Alternatively assume that the VT corner e g phase A has been grounded If phase B or C fault to ground the fault...

Страница 8: ...2 100 5 from the neutral When feeder cables are connected to the gen erator bus the additional capacitance dictates a much lower level of grounding resistance than achieved with a unit connected case...

Страница 9: ...hout pre loading For example assuming a pre fault 1pu rated load at 30 degree lag at one second the 3 phase fault value would be 2 4 times rated rather than 1 75 timesrated 1 30 1 75 90 2 4 69 Under t...

Страница 10: ...edapproach inhibits operation until the voltage drops below a preset voltage It should be set to function below about 80 of rated voltage with a current pickup of about 50 of generator rated Since the...

Страница 11: ...imes tap CDS220 or 0 4A 87G is representa tive of a recommended setting for a moderate mismatch in CT quality and burden Fig 13 also shows 51V relays to back up the 87G and external relays and breaker...

Страница 12: ...nchroniz ing when the generator is initially slower than the system Since motoring can occur during a large reactive power flow the real power component needs to be measured at low power factors The B...

Страница 13: ...y a mho circle centered about the X axis offset from the R axis by X d 2 Two zones sometimes are used a high speed zone and a time delayed zone FIG 19 LOSS OF EXCITATION USING IMPEDANCE RELAY With com...

Страница 14: ...r during a fault To prevent a 60FL from being declared during loss of station power it may be necessary to allow a 3 phase 60F to be declared only when some low level of load current exists FIGURE 22...

Страница 15: ...ach set point may be set to recognize either over frequency or underfrequency Multiple frequency set points are available in the BE1 81O U BE1 GPS100 BE1 951 and BE1 1051 Another common need for frequ...

Страница 16: ...ld be employed where protection independent of the plant is desired In this case the 67 relays would be placed in the switchyard rather than in the control room While directional overcurrent relay 67...

Страница 17: ...reaker depending on the type of fault that is detected For instance if the generator is protected by a 51V and an 87G and only the 51V trips it may be assumed that the fault is external to the generat...

Страница 18: ...EXAMPLE OF BARE MINIMUM PROTECTION LOW IMPEDANCE GROUNDING Fig 30 shows the suggested minimum protection with low resistance grounding It includes differential protection which provides fast selectiv...

Страница 19: ...ssive generator reactive absorption Ther mal relay 49 protects against stator overheating due to protracted heavy reactive power demands and loss of generator cooling Even if the excitation system is...

Страница 20: ...voltage balancerelay 60 field ground relay 64F frequency relay 81 and the 27 50 62 relay combination for inadvertent energization protection Relay 51GN provides a second means of detecting stator gro...

Страница 21: ...ures 34 through 37 show the BE1 GPS100 and BE1 CDS220 applied to generator protection Due to logic complexity full details are not shown Details of these applica tions may be found in the respective i...

Страница 22: ...20 FIGURE 35 BE1 GPS100 APPLIED TO HIGH IMPEDANCE GROUNDED GENERATOR HI_Z_GND PREPROGRAMMED LOGIC SEE INSTRUCTION MANUAL FOR LOGIC DETAILS...

Страница 23: ...FIGURE 36 BE1 CDS220 APPLIED TO GENERATOR FOR 87 PHASE 87 NEUTRAL AND 51 PHASE NEUTRAL GROUND AND NEGATIVE SEQUENCE 21...

Страница 24: ...s typical settings for use as a starting point in the setting determi nation procedure The proper settings are heavily influenced by the specifics of each application Typical settings are also used as...

Страница 25: ...urrent 49 20 StatorTemperature RTD Lower 95 C upper 105 C 50 87 12 Differentialviaflux PU 10 INOM or less if 1A relay may be used summationCTs 50 27 IE 24 InadvertentEnergization 50 0 5A 10 INOM Overc...

Страница 26: ...75 100 INOM GEN Definite Time 0 1 0 25 sec InadvertentEnergization Inst 200 INOM GEN 81 21 Over underfrequency Generator protection 57 62Hz 0 5s Island detection 59 61Hz 0 1s 87G 13 GeneratorPhase BE1...

Страница 27: ...9 59 X X X X X X 59N 27 3N 59N 59P 4 4 4 60FL 60 X X X 67IE 67 X X 81 81O U 81O U X X X X X 87G 87G X 87N 67N 87UD 87T X 1 50 51G Indicates a relay that monitors a ground CT source 2 50 51N Indicates...

Страница 28: ...54 2341 Fax 1 618 654 2351 BaslerElectricInternational P A E Les Pins 67319 Wasselonne Cedex FRANCE Phone 33 3 88 87 1010 Fax 33 3 88 87 0808 If you have any questions or need additionalinformation pl...

Отзывы: