Table 1 - Typical Settings
IEEE No. Fig.
Function
Typical Settings and Remarks
51VR
11
Voltage Restrained
PU: 175%
I
NOM
; Curve: V
I
; TD: 4.
Overcurrent
Zero Restraint Voltage: 100% V
NOM L-L
59N,
4
Ground Overvoltage
59N: 5% V
NEU
during HV terminal fault;
27-3N,
27-3N: 25% V
3rd
during normal operation; TD: 10s
59P
59P: 80% V
NOM
67
I
E
25
Directional O/C for
PU: 75-100%
I
NOM
GEN
; Definite Time (0.1-0.25 sec.)
Inadvertent Energization
Inst: 200%
I
NOM
GEN
81
21
Over/under frequency
Generator protection: 57, 62Hz, 0.5s;
Island detection: 59, 61Hz, 0.1s
87G
13
Generator Phase
BE1-87G: 0.4A;
Differential
BE1-CDS220: Min P.U.: 0.1 * Tap;
Tap:
I
NOM
; Slope: 15%
87N
8
Generator Ground
BE1-CDS220: Min P.U.: 0.1 times tap; Slope 15%;
Differential
Time delay: 0.1s; choose low tap
BE1-67N: current polarization; time: 0.25A; Curve: V
I
;
TD: 2; Instantaneous: disconnect
87UD
13
Unit Differential
BE1-87T or CDS220 Min PU:0.35*Tap;
Tap:
I
NOM
; Slope 30%
24