Table 1 - Typical Settings
IEEE No. Fig.
Function
Typical Settings and Remarks
24
21,
Overexcitation
PU: 1.1*V
NOM
/60; TD: 0.3; reset TD: 5
23
alarm P.U.: 1.18*V
NOM
/60
alarm delay: 2.5s
25
21,
Synchronism Check
Max Slip: 6RPM; Max phase angle error: 10°
28
Max V
MAG
error: 2.5% V
NOM
32
16,
Reverse Power
PU: turbine 1% of rated; 15 s
17
(one stage)
PU: Reciprocating engine: 10% of rated; 5 s
32-1
17
Reverse Power
PU: same as 32; 3 s
Nonelectrical Trip
Supervision
40
16,
Loss-of-field (VAR Flow
Level 1 PU: 60% VA rating; Delay: 0.2s;
18
Approach)
Level 2 PU: 100% VA rating: 0.1s
46
26
Negative Sequence
I
2
PU: 10%
I
rated
; K=10
Overcurrent
49
20
Stator Temperature (RTD) Lower: 95°C; upper: 105°C
50/87
12
Differential via flux
PU:10%
I
NOM
or less if 1A relay may be used
summation CTs
50/27
I
E
24
Inadvertent Energization
50: 0.5A (10%
I
NOM
)
Overcurrent with 27, 81
27: 85% V
NOM
(81: Similar)
Supervision
51N
3
Stator Ground Over-
PU: 10%
I
NOM
; curve: EI; TD: 4. Inst: none. Higher PU
current (Low, Med Z Gnd, required to coordinate with load.
Phase CT Residual)
No higher than 25%
I
NOM
.
50/51N
2
Stator Ground Over-
P.U.: 10%
I
NOM
;
Curve E
I
, TD4; Inst 100%
I
NOM
. Higher PU
current (Low, Med Z Gnd, if required to coordinate with load. No higher than
Neutral CT or Flux
25%
I
NOM
.
Summation CT)
51GN,
4,
Stator Ground Over-
PU: 10%
I
FAULT
at HV Term.; Curve: VI; TD:4.
51N
7
current (High Z Gnd)
51VC
11
Voltage Controlled
PU: 50%
I
NOM
; Curve: V
I
; TD: 4.
Overcurrent
Control voltage: 80%V
NOM
.
23