Manual 2100-603
Page
43 of 44
MODEL
RETURN
AIR
TEMP.
PRESSURE
AIR TEMPERATURE ENTERING OUTDOOR COIL
75°
80°
85°
90°
95°
100°
105°
110°
115°
Q24H2
75 DB
62 WB
Low Side
High Side
122
369
121
378
121
391
121
407
122
426
122
449
123
474
125
503
128
535
80 DB
67 WB
Low Side
High Side
130
378
129
388
129
401
129
417
130
437
131
460
132
486
134
516
137
549
85 DB
72 WB
Low Side
High Side
135
391
134
402
134
415
134
432
135
452
136
476
137
503
139
534
142
568
Q30H2
75 DB
62 WB
Low Side
High Side
122
360
123
377
124
398
126
419
128
444
130
470
132
498
134
528
136
561
80 DB
67 WB
Low Side
High Side
131
369
132
387
133
408
135
430
137
455
139
482
141
511
143
542
145
575
85 DB
72 WB
Low Side
High Side
136
382
137
401
138
422
140
445
142
471
144
499
146
529
148
561
150
595
Q36H2
75 DB
62 WB
Low Side
High Side
122
367
124
390
128
413
130
437
133
460
135
485
137
508
137
533
138
558
80 DB
67 WB
Low Side
High Side
130
376
133
400
137
424
139
448
142
472
144
497
146
521
147
547
148
572
85 DB
72 WB
Low Side
High Side
135
389
138
414
142
439
144
464
147
489
149
514
151
539
152
566
153
592
Q42H2
75 DB
62 WB
Low Side
High Side
118
372
121
394
123
416
125
440
128
465
130
491
132
520
134
549
136
579
80 DB
67 WB
Low Side
High Side
126
382
129
404
132
427
134
451
137
477
139
504
141
533
143
563
145
594
85 DB
72 WB
Low Side
High Side
130
395
134
418
137
442
139
467
142
494
144
522
146
552
148
583
150
615
Q48H2
75 DB
62 WB
Low Side
High Side
119
372
122
394
124
417
127
442
130
467
132
493
134
522
135
550
136
580
80 DB
67 WB
Low Side
High Side
127
382
130
404
133
428
136
453
139
479
141
506
143
535
144
564
145
595
85 DB
72 WB
Low Side
High Side
131
395
135
418
138
443
141
469
144
496
146
524
148
554
149
584
150
616
Q60H2
75 DB
62 WB
Low Side
High Side
108
378
109
395
111
413
114
435
116
458
119
485
121
513
123
544
126
577
80 DB
67 WB
Low Side
High Side
115
388
117
405
119
424
122
446
124
470
127
497
129
526
132
558
135
592
85 DB
72 WB
Low Side
High Side
119
402
121
419
123
439
126
462
128
486
131
514
134
544
137
578
140
613
Low side pressure ± 4 psig
High side pressure ± 10 psig
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the
system, the charge should be removed, system evacuated and recharged to serial plate instructions.
75°F outdoor temperature condenser fan motor is running on low speed.
When the system is operating in the dehumidification mode, the suction pressure will be reduced by 4 to 8 psig and the discharge
pressure will be reduced by 19 to 22 psig.
TABLE 10
COOLING PRESSURE
(ALL TEMPERATURES IN DEGREES F)
Содержание Q-TEC Q24H2D Series
Страница 6: ...Manual 2100 603 Page 6 of 44 FIGURE 1 UNIT DIMENSIONS Q24H2D Q60H2D Q30H2D Q36H2D Q42H2D Q48H2D...
Страница 9: ...Manual 2100 603 Page 9 of 44 FIGURE 6 DUCTED APPLICATION FIGURE 5 INSTALLATION WITH DUCT FREE PLENUM...
Страница 13: ...Manual 2100 603 Page 13 of 44 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...
Страница 15: ...Manual 2100 603 Page 15 of 44 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...
Страница 31: ...Manual 2100 603 Page 31 of 44 FIGURE 22 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...