background image

Manual 2100-603

Page 

29 of 44

SERVICE HINTS

  1.  Caution user to maintain clean air filters at all 

times.  Also, not to needlessly close off supply 

air registers.  This may reduce airflow through 

the system, which shortens equipment service 

life as well as increasing operating costs and 

noise levels.

  2.  Switching to heating cycle at 75°F or higher 

outside temperature may cause a nuisance trip 

of the remote reset high pressure switch.  Turn 

thermostat off, then on to reset the high pressure 

switch.

  3.  The heat pump wall thermostats perform 

multiple functions.  Be sure that all function 

switches are correctly set for the desired 

operating mode before trying to diagnose any 

reported service problems.

  4.  Check all power fuses or circuit breakers to be 

sure they are the correct rating.

  5.  Periodic cleaning of the outdoor coil to permit 

full and unrestricted airflow circulation is 

essential.

  6.  Some service requires the need to remove the 

unit from the wall including replacement of 

the indoor coil and/or the outdoor coil.  Also 

servicing the outdoor fan motor or fan blade 

will require removing the unit from the wall if 

the unit is installed at a height that is not easily 

accessible from the outside of the building.

    In order to remove the unit from the wall the 

following procedure must be used:

    a.  Turn off power to the unit at the remote  

  location.  Some units may have more than one   

  power supply.  

    b.  Disconnect field wiring at unit terminal block 

 

  and remove from unit.

    c.  Disconnect condensate drain.
    d.  Remove the lower skirting around the unit.
    e.  Remove wall mounting brackets from wall on  

  each side of the unit.

    f.  If unit is attached to duct work, remove upper  

  cabinet extension by removing the top center  

  screw only from the cabinet side panel.

    g.  Remove screws that attach the duct work to  

  the unit flanges.

    This unit is equipped with four rollers  

  mounted to the base.  For ease of pulling unit  

  out from the wall, you may want to remove the  

  bottom service door which requires removal of  

  the return air panel, and grip the front flange of 

 

  the base pan then pull straight out.

  7.  Annual maintenance is required to ensure that all 

of the systems are functioning properly.

    a.  Check to make sure that the drains are not  

  obstructed in any way. 

    b.  Remove any debris in the condenser section  

  of the unit.

    c.  Inspect and clean mist eliminator as described  

 below.

    d.  Inspect and wash outdoor coil as necessary.

MIST ELIMINATOR SERVICE

A mist eliminator is supplied with the wall sleeve.  The 

mist eliminator is constructed of an aluminum frame 

and mesh.  The mist eliminator is located in the top 

section of the wall sleeve and can be removed from the 

inside of the building without removing the unit from 

the wall.  This requires that the ventilation package 

must be removed.
It is recommended that the mist eliminator be inspected 

annually and serviced as required.  The mist eliminator 

can be inspected from the outside of the building by 

looking through the outdoor grille.  The mist eliminator 

can be serviced from the outside by using a vacuum 

cleaner.  The outdoor grille must be removed.  Use the 

vacuum to remove dirt and debris from the surface of 

the mist eliminator.  If additional cleaning is required, 

the mist eliminator will have to be removed from the 

sleeve.
The ventilation package will have to be removed to 

gain access to the mist eliminator.  If the blank off plate 

option is used, it is not necessary to service the mist 

eliminator.  The steps necessary to remove each of the 

vent options are listed below.
The mist eliminator can be cleaned by washing with 

soap and water.  The excess water should be shaken off 

the mist eliminator before it is reinstalled.

Содержание Q-TEC Q24H2D Series

Страница 1: ...Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 603 Supersedes NEW File Vol II Tab 14 Date 11 05 13 Models Q24H2D Q30H2D Q36H2D Q42H2D Q48H2D Q60H2D Q TEC SERIES PACK...

Страница 2: ...le 2 Electrical Specifications 5 Table 3 Operating Voltage Range 19 Table 4 Wall Thermostats 21 Table 5 Troubleshooting 38 Table 6 Temp vs Resistance of Temp Sensor 39 Table 7 Fan Blade Dimensions 42...

Страница 3: ...mmer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditio...

Страница 4: ...Ambient Control Outdoor Thermostat FILTER OPTIONS X 1 inch Fiberglass Standard F 2 inch Fiberglass P 2 inch Pleated Q 36 H 2 D A 10 X X X X X X CAPACITY 24 2 Ton 30 2 Ton 36 3 Ton 42 3 Ton 48 4 Ton 60...

Страница 5: ...0 30 14 10 10 10 14 10 10 10 Q48H2DA0Z A05 A10 A15 230 208 1 1 1 or 2 1 or 2 1 or 2 38 63 88 88 50 70 90 90 8 6 3 3 10 8 8 8 38 38 38 25 50 50 50 50 50 25 50 50 8 8 8 10 8 8 10 10 10 10 10 10 Q48H2DB0...

Страница 6: ...Manual 2100 603 Page 6 of 44 FIGURE 1 UNIT DIMENSIONS Q24H2D Q60H2D Q30H2D Q36H2D Q42H2D Q48H2D...

Страница 7: ...moved to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the skid See Figure 3 B The unit can be tipped forward and slid down the...

Страница 8: ...parate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly Start Procedure and any tags and or labels attached...

Страница 9: ...Manual 2100 603 Page 9 of 44 FIGURE 6 DUCTED APPLICATION FIGURE 5 INSTALLATION WITH DUCT FREE PLENUM...

Страница 10: ...ounts on top of the unit and has both vertically and horizontally adjustable louvers on the front discharge grille For hot water coil option a QPBHWxx F for free blow or QPBHWxx D for ducted airflow i...

Страница 11: ...he drain is to be routed through an unconditioned space it must be protected from freezing The drain line must be able to be removed from the unit if it is necessary to remove the unit from the wall W...

Страница 12: ...RE 11 REAR DRAIN TOP VIEW WALL MAXIMUM 10 FOR REAR DRAIN COUPLINGS NOT SHOWN BUT RECOMMENDED FOR EASE OF REMOVABILITY FOR SERVICE SLEEVE DRAIN LINE WALL BRACKET UNIT FIGURE 10 STANDARD REAR DRAIN FIGU...

Страница 13: ...Manual 2100 603 Page 13 of 44 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...

Страница 14: ...PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLU...

Страница 15: ...Manual 2100 603 Page 15 of 44 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...

Страница 16: ...RAIN PAN MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN...

Страница 17: ...le FIGURE 13A UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS CABINET SIDE PANEL ENLARGED VIEW OF MOUNTING BRACKET SHOWING SLEEVE TO CABINET ATTA...

Страница 18: ...ck both sides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessa...

Страница 19: ...the installed KW of electric heat there may be two field power circuits required If this is the case the unit serial plate will so indicate All models are suitable only for connection with copper wire...

Страница 20: ...during dehumidification mode the call for cooling takes precedence over the dehumidification and the unit will cool until the thermostat is satisfied Once the call for cooling is satisfied the unit m...

Страница 21: ...may result in motor failure FIGURE 16 TABLE 4 WALL THERMOSTATS CONTROLS MIS 1285 Thermostat Predominant Features 8403 067 Carbon Dioxide Sensor with LCD for Sensor Readings 8403 060 1120 445 3 stage C...

Страница 22: ...te Black White Black White Black Red Yellow Plug 4 2 3 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 12 W1 E 4102 063 B 8403 060 SC With X Thermostat Option FACTORY INSTALLED JUMPER 1 Dehumidificati...

Страница 23: ...ellow Plug 4 2 3 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 12 Red White MIS 2690 C 6 5 And Demand Ventilation FACTORY INSTALLED JUMPER 1 With X Thermostat Option Dehumidification Wiring Diagram...

Страница 24: ...Diagram Thermostat Plug 2 Pink Red White Brown Blue Yellow Orange Brown White Purple White Black White Brown Blue Yellow Orange Brown White Purple White Red Red White Red White Red White 1 2 3 4 5 Plu...

Страница 25: ...og Out CO Controller Bard Part 8403 067 2 2 1 2 3 4 5 6 Red White 1 COM Yellow Orange Thermostat Blue Brown Red White Black White Red White 4102 066 B Plug 4 1 2 3 4 5 6 7 8 9 10 11 12 L C R W2 B W1 E...

Страница 26: ...ermostat Plug 2 Pink Red White Brown Blue Yellow Orange Brown White Purple White Black White Brown Blue Yellow Orange Brown White Purple White Red Red White Red White Red White Black White Black White...

Страница 27: ...e leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be use...

Страница 28: ...age due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light and the compressor co...

Страница 29: ...cabinet side panel g Remove screws that attach the duct work to the unit flanges This unit is equipped with four rollers mounted to the base For ease of pulling unit out from the wall you may want to...

Страница 30: ...gh the opening in the back of the unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed Q Tec ENERGY RECOVERY VENTILATOR Option Before starti...

Страница 31: ...Manual 2100 603 Page 31 of 44 FIGURE 22 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Страница 32: ...Manual 2100 603 Page 32 of 44 FIGURE 23 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Страница 33: ...g to hold the ball on the seat This will make the method of checking the ball freedom with a magnet difficult Refer to Figures 25 and 26 for the location of the check valve and drain back capillary Wh...

Страница 34: ...OR REHEAT COIL Figure 25 shows the refrigerant gas flow through the reheat coil during the dehumidification mode When the unit is in standard cooling Figure 26 or heating mode the reheat coil is inact...

Страница 35: ...perating pressures can be observed Pressure curves can be found later in the manual covering all models on both cooling and heating cycles It is imperative to match the correct pressure curve to the u...

Страница 36: ...erwise the timing will remain accelerated and run through the 1 minute minimum defrost length sequence in a matter of seconds and will automatically terminate the defrost sequence There is an initiate...

Страница 37: ...44 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED RUN TIME SELECTOR FACTORY SETTING 30 MIN MIS 2684 A ON OFF FIGU...

Страница 38: ...eck for 24V between RV C and B C 1 Check control circuit wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replace solenoid coil Unit will not g...

Страница 39: ...43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757 64 0 13820 102...

Страница 40: ...s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check f...

Страница 41: ...ion d Add a drip loop to the cables so that water cannot enter the motor by draining down the cables Refer to Figure 26 The installation is now complete Reapply the AC power to the HVAC equipment and...

Страница 42: ...of refrigerant listed on the serial plate AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity Reference Table 8 The following pressure tables show nom...

Страница 43: ...w Side High Side 126 382 129 404 132 427 134 451 137 477 139 504 141 533 143 563 145 594 85 DB 72 WB Low Side High Side 130 395 134 418 137 442 139 467 142 494 144 522 146 552 148 583 150 615 Q48H2 75...

Страница 44: ...Cooling Mode Unoccupied 1 X X X X X X X Cooling Mode Occupied 1 X X X X X 1st Stage Heating Occupied 2 X X X X X X X X X 1st Stage Heating Unoccupied 2 X X X X X X X 2nd Stage Heating Occupied 3 X X...

Отзывы: