Manual 2100-603
Page
11 of 44
FRESH AIR INTAKE
This unit is equipped with a fresh air damper assembly.
The damper blade is locked in the closed position
when the unit is shipped from the factory. To allow
the damper to operate remove the two plastic locking
pins, one on each end of the blade. This will allow for
maximum fresh airflow. The damper blade will now
open when the indoor blower is operating. If less than
maximum fresh airflow is required, reinsert the plastic
pins to limit damper blade opening to desired level.
Two extra pins are provided (taped to the inside of the
assembly) which may be used to hold the blade in some
position other than minimum or maximum position.
This fresh air assembly is located in the rear of the unit
and to gain access to make these adjustments remove
the air filter service door.
All capacity, efficiency and cost of operation
information as required for Department of Energy
“Energyguide” Fact Sheets are based upon the fresh
air blank-off plate in place and is recommended for
maximum energy efficiency.
The blank-off plate is available upon request from the
factory and is installed in place of the fresh air damper
shipped with each unit.
For details on energy recovery ventilation see separate
section.
SERVICE LIGHT
The unit is equipped with a service light, which signals
the user that service is required. The light is located
in the upper control panel and is visible only when the
hinged service/filter access door is open.
The
Service Unit
light indicates that the unit has
been shut off by a high or low pressure device. This
indicates that the unit needs to be serviced.
CONDENSATE DRAIN
There are two drain connections on the unit. The rear
drain is the primary drain, and is located on the right
lower rear panel of the unit. The optional side drain is
located on the bottom right side of the unit. The side
drain is shipped with a plug installed.
The
side drain
requires a water trap for proper drainage.
See Figure 9. The drain can be routed through the floor
or through the wall.
If the drain is to be routed through
an unconditioned space, it must be protected from
freezing.
The drain line must be able to be removed
from the unit if it is necessary to remove the unit from
the wall. When the side drain is used, the plug must be
removed and installed in the rear drain outlet.
The
rear drain
can be used with wall thickness of up to
10 inches where a water trap can be installed between
the unit and the interior wall. See Figure 10. The trap
cannot extend beyond the edge of the unit or it will
interfere with the wall mounting bracket. The drain can
be routed through the floor or through the wall. If the
drain is routed through the wall, the drain line must be
positioned such that it will not interfere with the sleeve
flange or the grille. See Figure 11.
If the drain is to
be routed through an unconditioned space, it must be
protected from freezing.
OPTIONAL REAR DRAIN KITS
Optional Rear Drain Kit, Bard Model QCDS48A, is also
available for these products. The optional rear drain kit
offers multiple benefits that include the following:
• Allows unit to be rolled away from the sleeve
without having to disconnect any hard plumbing
connections.
• Allows indoor coil condensate to be easily
connected to Rear Drain Box while bypassing the
outdoor coil drain pan. This aids in minimizing the
potential for biological growth to occur by
minimizing the standing water and exposing it to
warm temperatures.
See Figures 12A, 12B, 12C and 12D.
The drain box permanently mounts onto the wall sleeve
and is then either piped directly outdoors, or can be
piped vertically. The Q-Tec unit is then equipped with
fittings on the rear of the unit that slide into the drain
box as it is wheeled towards the wall sleeve.
NOTE:
On models equipped with a refrigerant
subcooler in the lower drain pan may experience a
2-3% decrease in cooling performance and efficiency
when the indoor condensate is routed around the
outdoor coil drain pan/subcooler assembly. Unit
rated performance and efficiency are with the indoor
condensate routed to the outdoor coil pan.
There is also a heated version of the rear drain box
available (Model #QCDS48H) for installation in northern
climates where freezing may occur.
NOTE:
Additional
circuit needed for drain heater.
Содержание Q-TEC Q24H2D Series
Страница 6: ...Manual 2100 603 Page 6 of 44 FIGURE 1 UNIT DIMENSIONS Q24H2D Q60H2D Q30H2D Q36H2D Q42H2D Q48H2D...
Страница 9: ...Manual 2100 603 Page 9 of 44 FIGURE 6 DUCTED APPLICATION FIGURE 5 INSTALLATION WITH DUCT FREE PLENUM...
Страница 13: ...Manual 2100 603 Page 13 of 44 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...
Страница 15: ...Manual 2100 603 Page 15 of 44 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...
Страница 31: ...Manual 2100 603 Page 31 of 44 FIGURE 22 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...