background image

Manual 2100-603

Page 

11 of 44

FRESH AIR INTAKE

This unit is equipped with a fresh air damper assembly.  

The damper blade is locked in the closed position 

when the unit is shipped from the factory.  To allow 

the damper to operate remove the two plastic locking 

pins, one on each end of the blade.  This will allow for 

maximum fresh airflow.  The damper blade will now 

open when the indoor blower is operating.  If less than 

maximum fresh airflow is required, reinsert the plastic 

pins to limit damper blade opening to desired level.  

Two extra pins are provided (taped to the inside of the 

assembly) which may be used to hold the blade in some 

position other than minimum or maximum position.  

This fresh air assembly is located in the rear of  the unit 

and to gain access to make these adjustments remove 

the air filter service door.
All capacity, efficiency and cost of operation 

information as required for Department of Energy 

“Energyguide” Fact Sheets are based upon the fresh 

air blank-off plate in place and is recommended for 

maximum energy efficiency.

The blank-off plate is available upon request from the 

factory and is installed in place of the fresh air damper 

shipped with each unit.
For details on energy recovery ventilation see separate 

section.

SERVICE LIGHT

The unit is equipped with a service light, which signals 

the user that service is required.  The light is located 

in the upper control panel and is visible only when the 

hinged service/filter access door is open.

The 

Service Unit

 light indicates that the unit has 

been shut off by a high or low pressure device.  This 

indicates that the unit needs to be serviced.

CONDENSATE DRAIN

There are two drain connections on the unit.  The rear 

drain is the primary drain, and is located on the right 

lower rear panel of the unit.  The optional side drain is 

located on the bottom right side of the unit.  The side 

drain is shipped with a plug installed.
The 

side drain

 requires a water trap for proper drainage.  

See Figure 9.  The drain can be routed through the floor 

or through the wall.  

If the drain is to be routed through 

an unconditioned space, it must be protected from 
freezing

 The drain line must be able to be removed 

from the unit if it is necessary to remove the unit from 

the wall.  When the side drain is used, the plug must be 

removed and installed in the rear drain outlet.

The 

rear drain

 can be used with wall thickness of up to 

10 inches where a water trap can be installed between 

the unit and the interior wall.  See Figure 10.  The trap 

cannot extend beyond the edge of the unit or it will 

interfere with the wall mounting bracket.  The drain can 

be routed through the floor or through the wall.  If the 

drain is routed through the wall, the drain line must be 

positioned such that it will not interfere with  the sleeve 

flange or the grille.  See Figure 11.  

If the drain is to 

be routed through an unconditioned space, it must be 
protected from freezing.

OPTIONAL REAR DRAIN KITS

Optional Rear Drain Kit, Bard Model QCDS48A, is also 

available for these products.  The optional rear drain kit 

offers multiple benefits that include the following:

  •  Allows unit to be rolled away from the sleeve    

    without having to disconnect any hard plumbing  

  connections.

  •  Allows indoor coil condensate to be easily  

 

    connected to Rear Drain Box while bypassing the  

    outdoor coil drain pan.  This aids in minimizing the  

    potential for biological growth to occur by  

 

    minimizing the standing water and exposing it to  

  warm temperatures.

See Figures 12A, 12B, 12C and 12D.

The drain box permanently mounts onto the wall sleeve 

and is then either piped directly outdoors, or can be 

piped vertically.  The Q-Tec unit is then equipped with 

fittings on the rear of the unit that slide into the drain 

box as it is wheeled towards the wall sleeve.

NOTE:

 

On models equipped with a refrigerant 

subcooler in the lower drain pan may experience a 

2-3% decrease in cooling performance and efficiency 

when the indoor condensate is routed around the 
outdoor coil drain pan/subcooler assembly.  Unit 

rated performance and efficiency are with the indoor 

condensate routed to the outdoor coil pan.

There is also a heated version of the rear drain box 

available (Model #QCDS48H) for installation in northern 

climates where freezing may occur.  

NOTE:

 

Additional 

circuit needed for drain heater.

Содержание Q-TEC Q24H2D Series

Страница 1: ...Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 603 Supersedes NEW File Vol II Tab 14 Date 11 05 13 Models Q24H2D Q30H2D Q36H2D Q42H2D Q48H2D Q60H2D Q TEC SERIES PACK...

Страница 2: ...le 2 Electrical Specifications 5 Table 3 Operating Voltage Range 19 Table 4 Wall Thermostats 21 Table 5 Troubleshooting 38 Table 6 Temp vs Resistance of Temp Sensor 39 Table 7 Fan Blade Dimensions 42...

Страница 3: ...mmer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditio...

Страница 4: ...Ambient Control Outdoor Thermostat FILTER OPTIONS X 1 inch Fiberglass Standard F 2 inch Fiberglass P 2 inch Pleated Q 36 H 2 D A 10 X X X X X X CAPACITY 24 2 Ton 30 2 Ton 36 3 Ton 42 3 Ton 48 4 Ton 60...

Страница 5: ...0 30 14 10 10 10 14 10 10 10 Q48H2DA0Z A05 A10 A15 230 208 1 1 1 or 2 1 or 2 1 or 2 38 63 88 88 50 70 90 90 8 6 3 3 10 8 8 8 38 38 38 25 50 50 50 50 50 25 50 50 8 8 8 10 8 8 10 10 10 10 10 10 Q48H2DB0...

Страница 6: ...Manual 2100 603 Page 6 of 44 FIGURE 1 UNIT DIMENSIONS Q24H2D Q60H2D Q30H2D Q36H2D Q42H2D Q48H2D...

Страница 7: ...moved to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the skid See Figure 3 B The unit can be tipped forward and slid down the...

Страница 8: ...parate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly Start Procedure and any tags and or labels attached...

Страница 9: ...Manual 2100 603 Page 9 of 44 FIGURE 6 DUCTED APPLICATION FIGURE 5 INSTALLATION WITH DUCT FREE PLENUM...

Страница 10: ...ounts on top of the unit and has both vertically and horizontally adjustable louvers on the front discharge grille For hot water coil option a QPBHWxx F for free blow or QPBHWxx D for ducted airflow i...

Страница 11: ...he drain is to be routed through an unconditioned space it must be protected from freezing The drain line must be able to be removed from the unit if it is necessary to remove the unit from the wall W...

Страница 12: ...RE 11 REAR DRAIN TOP VIEW WALL MAXIMUM 10 FOR REAR DRAIN COUPLINGS NOT SHOWN BUT RECOMMENDED FOR EASE OF REMOVABILITY FOR SERVICE SLEEVE DRAIN LINE WALL BRACKET UNIT FIGURE 10 STANDARD REAR DRAIN FIGU...

Страница 13: ...Manual 2100 603 Page 13 of 44 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...

Страница 14: ...PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLU...

Страница 15: ...Manual 2100 603 Page 15 of 44 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...

Страница 16: ...RAIN PAN MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN...

Страница 17: ...le FIGURE 13A UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS CABINET SIDE PANEL ENLARGED VIEW OF MOUNTING BRACKET SHOWING SLEEVE TO CABINET ATTA...

Страница 18: ...ck both sides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessa...

Страница 19: ...the installed KW of electric heat there may be two field power circuits required If this is the case the unit serial plate will so indicate All models are suitable only for connection with copper wire...

Страница 20: ...during dehumidification mode the call for cooling takes precedence over the dehumidification and the unit will cool until the thermostat is satisfied Once the call for cooling is satisfied the unit m...

Страница 21: ...may result in motor failure FIGURE 16 TABLE 4 WALL THERMOSTATS CONTROLS MIS 1285 Thermostat Predominant Features 8403 067 Carbon Dioxide Sensor with LCD for Sensor Readings 8403 060 1120 445 3 stage C...

Страница 22: ...te Black White Black White Black Red Yellow Plug 4 2 3 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 12 W1 E 4102 063 B 8403 060 SC With X Thermostat Option FACTORY INSTALLED JUMPER 1 Dehumidificati...

Страница 23: ...ellow Plug 4 2 3 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 12 Red White MIS 2690 C 6 5 And Demand Ventilation FACTORY INSTALLED JUMPER 1 With X Thermostat Option Dehumidification Wiring Diagram...

Страница 24: ...Diagram Thermostat Plug 2 Pink Red White Brown Blue Yellow Orange Brown White Purple White Black White Brown Blue Yellow Orange Brown White Purple White Red Red White Red White Red White 1 2 3 4 5 Plu...

Страница 25: ...og Out CO Controller Bard Part 8403 067 2 2 1 2 3 4 5 6 Red White 1 COM Yellow Orange Thermostat Blue Brown Red White Black White Red White 4102 066 B Plug 4 1 2 3 4 5 6 7 8 9 10 11 12 L C R W2 B W1 E...

Страница 26: ...ermostat Plug 2 Pink Red White Brown Blue Yellow Orange Brown White Purple White Black White Brown Blue Yellow Orange Brown White Purple White Red Red White Red White Red White Black White Black White...

Страница 27: ...e leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be use...

Страница 28: ...age due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light and the compressor co...

Страница 29: ...cabinet side panel g Remove screws that attach the duct work to the unit flanges This unit is equipped with four rollers mounted to the base For ease of pulling unit out from the wall you may want to...

Страница 30: ...gh the opening in the back of the unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed Q Tec ENERGY RECOVERY VENTILATOR Option Before starti...

Страница 31: ...Manual 2100 603 Page 31 of 44 FIGURE 22 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Страница 32: ...Manual 2100 603 Page 32 of 44 FIGURE 23 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Страница 33: ...g to hold the ball on the seat This will make the method of checking the ball freedom with a magnet difficult Refer to Figures 25 and 26 for the location of the check valve and drain back capillary Wh...

Страница 34: ...OR REHEAT COIL Figure 25 shows the refrigerant gas flow through the reheat coil during the dehumidification mode When the unit is in standard cooling Figure 26 or heating mode the reheat coil is inact...

Страница 35: ...perating pressures can be observed Pressure curves can be found later in the manual covering all models on both cooling and heating cycles It is imperative to match the correct pressure curve to the u...

Страница 36: ...erwise the timing will remain accelerated and run through the 1 minute minimum defrost length sequence in a matter of seconds and will automatically terminate the defrost sequence There is an initiate...

Страница 37: ...44 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED RUN TIME SELECTOR FACTORY SETTING 30 MIN MIS 2684 A ON OFF FIGU...

Страница 38: ...eck for 24V between RV C and B C 1 Check control circuit wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replace solenoid coil Unit will not g...

Страница 39: ...43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757 64 0 13820 102...

Страница 40: ...s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check f...

Страница 41: ...ion d Add a drip loop to the cables so that water cannot enter the motor by draining down the cables Refer to Figure 26 The installation is now complete Reapply the AC power to the HVAC equipment and...

Страница 42: ...of refrigerant listed on the serial plate AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity Reference Table 8 The following pressure tables show nom...

Страница 43: ...w Side High Side 126 382 129 404 132 427 134 451 137 477 139 504 141 533 143 563 145 594 85 DB 72 WB Low Side High Side 130 395 134 418 137 442 139 467 142 494 144 522 146 552 148 583 150 615 Q48H2 75...

Страница 44: ...Cooling Mode Unoccupied 1 X X X X X X X Cooling Mode Occupied 1 X X X X X 1st Stage Heating Occupied 2 X X X X X X X X X 1st Stage Heating Unoccupied 2 X X X X X X X 2nd Stage Heating Occupied 3 X X...

Отзывы: