background image

Manual 2100-603

Page 

38 of 44

TROUBLESHOOTING

Sympton

Description, Check & Possible Causes

What & How to Check / Repair

Compressor 

will not start 

(heating or 

cooling)

1.  Check for LED illumination.

Is there an LED illuminated on the board (flashing)?

Yes = go to Step #2; No = go to Step #3

2.  Check for error codes.

Is the LED flashing a Code?

Yes = go to Step #4; No = go to Step #8

3.  Check for power at board.

Is there 24 volts AC between R and C?

Yes = go to Step #13; No = go to Step #9

4.  Check codes.

What code is blinking?

Code "1", go to Step #6; Code "2", go to Step#7; Fast Blink, go to Step #5

5.  Compressor delay active.

Wait for 5 minute delay or jump board's "speed up pins". Check for proper operation; if still needed, go back to Step #1.

6.  Low pressure fault.

Check wiring circuit and unit pressures.

7.  High pressure fault.

Check wiring circuit and unit pressures.

8.  Check for Compressor input signal.

Is there 24 volts AC between Y and C?

Yes = go to Step #10; No = go to Step #11

9.  No power to board.

The unit either does not have unit voltage, the transformer is bad or the unit wiring is incorrect.

10.  Check for Compressor output signal.

Is there 24 volts AC between CC & C?

Yes = go to Step #12; No = go to Step #13

11.  No "Y" compressor input signal.

Check thermostat wiring, incorrect phase of unit (see section on Phase Monitor), and finally unit wiring.

12.  No "CC" compressor output signal.

Check compressor contactor for proper operation and finally check compressor.

13.  Faulty board.

Replace defrost board.

Fan outdoor 

motor does 

not run  

(cooling or 

heating except 

during defrost)

Heat pump control defective

Check across fan relay on heat pump control. (Com-NC)

Replace heat pump control.

Motor defective

Check for open or shorted motor winding.  Replace motor.

Motor capacitor defective

Check capacitor rating.  Check for open or shorted capacitor.  Replace capacitor.

Reversing 

valve does not 

energize

(heating only)

Heat pump control defective

Check for 24V between RV-C and B-C.

1. Check control circuit wiring.

2. Replace heat pump control.

Reversing valve solenoid coil defective

Check for open or shorted coil.

Replace solenoid coil.

Unit will not go 

into defrost

(heating only)

Temperature sensor or heat pump control defective

Disconnect temperature sensor from board and jumper across "SPEEDUP" terminals and "SEN 

JMP" terminals.  This should cause the unit to go through a defrost cycle within one minute.

1. If unit goes through defrost cycle, replace temperature sensor.

2. If unit does not go through defrost cycle, replace heat pump control.

Unit will not 

come out of 

defrost

(heating only)

Temperature sensor or heat pump control defective

Jumper across "SPEEDUP" terminal.

This should cause the unit to come out of defrost within one minute. 

1. If unit comes out of defrost cycle, replace temperature sensor.

2. If unit does not come out of defrost cycle, replace heat pump control.

TABLE  5

TROUBLESHOOTING

NOTE:  If there was no power to 24 volt transformer,  
 

the compressor and outdoor fan motor will  

 

not start for 5 minutes.  This is because of   

 

the compressor short cycle protection. 

LED BLINK CODES

BLINK  FUNCTION

Slow 

Normal function (1.0 sec on/1.0 sec off)

Fast 

Compressor Delay timer active (0.1 sec on/0.1 sec off)

Low pressure switch failure

High pressure switch failure/“Soft” Lockout

Defrost mode active

High pressure switch failure/“Hard” Lockout

SOLID STATE HEAT PUMP CONTROL 

TROUBLESHOOTING PROCEDURE

 1. 

NOTE:

 

A thorough understanding of the defrost  

   

cycle sequence is essential.  Review that section  

   

earlier in this manual prior to troubleshooting the  

   

control.  

Turn on AC power supply to unit.

  2.  Turn thermostat blower switch to “fan on” – the  

    indoor blower should start.  (If it doesn’t,  

 

    troubleshoot indoor unit and correct problem.)
  3.  Turn thermostat blower to “auto” position.  Indoor  

    blower should stop.  

NOTE:

 

Many models have a  

   

1-minute blower time delay on “off” command;  

   

wait for this to time-out.

  4.  Set system switch to “heat” or “cool”.  Adjust    

    thermostat to call for heat or cool.  The indoor    

    blower, compressor  and outdoor fan should start.

Содержание Q-TEC Q24H2D Series

Страница 1: ...Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 603 Supersedes NEW File Vol II Tab 14 Date 11 05 13 Models Q24H2D Q30H2D Q36H2D Q42H2D Q48H2D Q60H2D Q TEC SERIES PACK...

Страница 2: ...le 2 Electrical Specifications 5 Table 3 Operating Voltage Range 19 Table 4 Wall Thermostats 21 Table 5 Troubleshooting 38 Table 6 Temp vs Resistance of Temp Sensor 39 Table 7 Fan Blade Dimensions 42...

Страница 3: ...mmer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditio...

Страница 4: ...Ambient Control Outdoor Thermostat FILTER OPTIONS X 1 inch Fiberglass Standard F 2 inch Fiberglass P 2 inch Pleated Q 36 H 2 D A 10 X X X X X X CAPACITY 24 2 Ton 30 2 Ton 36 3 Ton 42 3 Ton 48 4 Ton 60...

Страница 5: ...0 30 14 10 10 10 14 10 10 10 Q48H2DA0Z A05 A10 A15 230 208 1 1 1 or 2 1 or 2 1 or 2 38 63 88 88 50 70 90 90 8 6 3 3 10 8 8 8 38 38 38 25 50 50 50 50 50 25 50 50 8 8 8 10 8 8 10 10 10 10 10 10 Q48H2DB0...

Страница 6: ...Manual 2100 603 Page 6 of 44 FIGURE 1 UNIT DIMENSIONS Q24H2D Q60H2D Q30H2D Q36H2D Q42H2D Q48H2D...

Страница 7: ...moved to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the skid See Figure 3 B The unit can be tipped forward and slid down the...

Страница 8: ...parate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly Start Procedure and any tags and or labels attached...

Страница 9: ...Manual 2100 603 Page 9 of 44 FIGURE 6 DUCTED APPLICATION FIGURE 5 INSTALLATION WITH DUCT FREE PLENUM...

Страница 10: ...ounts on top of the unit and has both vertically and horizontally adjustable louvers on the front discharge grille For hot water coil option a QPBHWxx F for free blow or QPBHWxx D for ducted airflow i...

Страница 11: ...he drain is to be routed through an unconditioned space it must be protected from freezing The drain line must be able to be removed from the unit if it is necessary to remove the unit from the wall W...

Страница 12: ...RE 11 REAR DRAIN TOP VIEW WALL MAXIMUM 10 FOR REAR DRAIN COUPLINGS NOT SHOWN BUT RECOMMENDED FOR EASE OF REMOVABILITY FOR SERVICE SLEEVE DRAIN LINE WALL BRACKET UNIT FIGURE 10 STANDARD REAR DRAIN FIGU...

Страница 13: ...Manual 2100 603 Page 13 of 44 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...

Страница 14: ...PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLU...

Страница 15: ...Manual 2100 603 Page 15 of 44 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...

Страница 16: ...RAIN PAN MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN...

Страница 17: ...le FIGURE 13A UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS CABINET SIDE PANEL ENLARGED VIEW OF MOUNTING BRACKET SHOWING SLEEVE TO CABINET ATTA...

Страница 18: ...ck both sides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessa...

Страница 19: ...the installed KW of electric heat there may be two field power circuits required If this is the case the unit serial plate will so indicate All models are suitable only for connection with copper wire...

Страница 20: ...during dehumidification mode the call for cooling takes precedence over the dehumidification and the unit will cool until the thermostat is satisfied Once the call for cooling is satisfied the unit m...

Страница 21: ...may result in motor failure FIGURE 16 TABLE 4 WALL THERMOSTATS CONTROLS MIS 1285 Thermostat Predominant Features 8403 067 Carbon Dioxide Sensor with LCD for Sensor Readings 8403 060 1120 445 3 stage C...

Страница 22: ...te Black White Black White Black Red Yellow Plug 4 2 3 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 12 W1 E 4102 063 B 8403 060 SC With X Thermostat Option FACTORY INSTALLED JUMPER 1 Dehumidificati...

Страница 23: ...ellow Plug 4 2 3 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 12 Red White MIS 2690 C 6 5 And Demand Ventilation FACTORY INSTALLED JUMPER 1 With X Thermostat Option Dehumidification Wiring Diagram...

Страница 24: ...Diagram Thermostat Plug 2 Pink Red White Brown Blue Yellow Orange Brown White Purple White Black White Brown Blue Yellow Orange Brown White Purple White Red Red White Red White Red White 1 2 3 4 5 Plu...

Страница 25: ...og Out CO Controller Bard Part 8403 067 2 2 1 2 3 4 5 6 Red White 1 COM Yellow Orange Thermostat Blue Brown Red White Black White Red White 4102 066 B Plug 4 1 2 3 4 5 6 7 8 9 10 11 12 L C R W2 B W1 E...

Страница 26: ...ermostat Plug 2 Pink Red White Brown Blue Yellow Orange Brown White Purple White Black White Brown Blue Yellow Orange Brown White Purple White Red Red White Red White Red White Black White Black White...

Страница 27: ...e leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be use...

Страница 28: ...age due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light and the compressor co...

Страница 29: ...cabinet side panel g Remove screws that attach the duct work to the unit flanges This unit is equipped with four rollers mounted to the base For ease of pulling unit out from the wall you may want to...

Страница 30: ...gh the opening in the back of the unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed Q Tec ENERGY RECOVERY VENTILATOR Option Before starti...

Страница 31: ...Manual 2100 603 Page 31 of 44 FIGURE 22 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Страница 32: ...Manual 2100 603 Page 32 of 44 FIGURE 23 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Страница 33: ...g to hold the ball on the seat This will make the method of checking the ball freedom with a magnet difficult Refer to Figures 25 and 26 for the location of the check valve and drain back capillary Wh...

Страница 34: ...OR REHEAT COIL Figure 25 shows the refrigerant gas flow through the reheat coil during the dehumidification mode When the unit is in standard cooling Figure 26 or heating mode the reheat coil is inact...

Страница 35: ...perating pressures can be observed Pressure curves can be found later in the manual covering all models on both cooling and heating cycles It is imperative to match the correct pressure curve to the u...

Страница 36: ...erwise the timing will remain accelerated and run through the 1 minute minimum defrost length sequence in a matter of seconds and will automatically terminate the defrost sequence There is an initiate...

Страница 37: ...44 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED RUN TIME SELECTOR FACTORY SETTING 30 MIN MIS 2684 A ON OFF FIGU...

Страница 38: ...eck for 24V between RV C and B C 1 Check control circuit wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replace solenoid coil Unit will not g...

Страница 39: ...43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757 64 0 13820 102...

Страница 40: ...s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check f...

Страница 41: ...ion d Add a drip loop to the cables so that water cannot enter the motor by draining down the cables Refer to Figure 26 The installation is now complete Reapply the AC power to the HVAC equipment and...

Страница 42: ...of refrigerant listed on the serial plate AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity Reference Table 8 The following pressure tables show nom...

Страница 43: ...w Side High Side 126 382 129 404 132 427 134 451 137 477 139 504 141 533 143 563 145 594 85 DB 72 WB Low Side High Side 130 395 134 418 137 442 139 467 142 494 144 522 146 552 148 583 150 615 Q48H2 75...

Страница 44: ...Cooling Mode Unoccupied 1 X X X X X X X Cooling Mode Occupied 1 X X X X X 1st Stage Heating Occupied 2 X X X X X X X X X 1st Stage Heating Unoccupied 2 X X X X X X X 2nd Stage Heating Occupied 3 X X...

Отзывы: