Manual 2100-603
Page
44 of 44
MODEL
RETURN
AIR
TEMP.
PRESSURE
AIR TEMPERATURE ENTERING OUTDOOR COIL
0
5
10
15
20
25
30
35
40
45
50
55
60
65
Q24H2D
70
Low Side
High Side
35
273
42
284
49
295
56
307
62
318
69
329
76
340
83
351
89
362
96
374
103
385
110
396
116
407
123
418
Q30H2D
70
Low Side
High Side
33
278
40
290
47
303
54
315
61
327
67
340
74
352
81
364
88
377
95
389
102
401
109
414
116
426
122
438
Q36H2D
70
Low Side
High Side
33
266
40
275
47
285
53
295
60
305
67
315
74
325
80
334
87
344
94
354
100
364
107
374
114
384
121
393
Q42H2D
70
Low Side
High Side
29
265
36
275
42
286
49
296
56
306
63
317
70
327
77
337
83
347
90
358
97
368
104
378
111
389
117
399
Q48H2D
70
Low Side
High Side
31
268
37
280
44
291
51
302
58
314
64
325
71
336
78
348
85
359
92
370
98
382
105
393
112
404
119
416
Q60H2D
70
Low Side
High Side
22
257
30
270
37
282
44
295
52
308
59
320
66
333
73
346
81
358
88
371
95
384
103
396
110
409
117
422
TABLE 11
HEATING PRESSURE
(ALL TEMPERATURES IN DEGREES F)
Inputs to Board
Outputs From Board
NOTES
G
Y
B
W2 E1 A1
D RAT G1 BK YO RV
W
E1 A2 TWV
Cooling Mode Unoccupied
1
X
X
X
X
X
X
X
Cooling Mode Occupied
1
X
X
X
X
X
1st Stage Heating Occupied
2
X
X
X
X
X
X
X
X
X
1st Stage Heating Unoccupied
2
X
X
X
X
X
X
X
2nd Stage Heating Occupied
3
X
X
X
X
X
X
X
X
X
X
X
2nd Stage Heating Unoccupied
3
X
X
X
X
X
X
X
X
X
Emergency Heat
X
X
X
X
X
X
Dehumidification Occupied
4
X
X
X
X
X
X
Dehumidification Unoccupied
4
X
5
5
5
5
Dehumidification w/RAT Closed
X
X
X
X
X
X
X
Fan Only Occupied
X
X
X
X
Fan Only Unoccupied
X
X
TABLE 12
DEHUMIDIFICATION RELAY LOGIC BOARD
NOTES:
1. Cooling takes precedence over dehumidification. A cooling call will cancel dehumidification.
2. Dehumidification takes precedence over first stage heating.
3. A second stage heating call cancels dehumidification.
4. The relay logic board has a jumper on it to choose between full-time dehumidification and occupied dehumidification only. With
the jumper in the 1-2 position dehumidification is available full-time. With the jumper in the 2-3 position dehumidification is
available only when the room is occupied. The room is considered occupied when the A1 terminal is energized.
5. These outputs will be energized if the jumper is in the full time dehumidification position. They will be off if the jumper is in the
occupied dehumidification only position.
Содержание Q-TEC Q24H2D Series
Страница 6: ...Manual 2100 603 Page 6 of 44 FIGURE 1 UNIT DIMENSIONS Q24H2D Q60H2D Q30H2D Q36H2D Q42H2D Q48H2D...
Страница 9: ...Manual 2100 603 Page 9 of 44 FIGURE 6 DUCTED APPLICATION FIGURE 5 INSTALLATION WITH DUCT FREE PLENUM...
Страница 13: ...Manual 2100 603 Page 13 of 44 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...
Страница 15: ...Manual 2100 603 Page 15 of 44 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...
Страница 31: ...Manual 2100 603 Page 31 of 44 FIGURE 22 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...