/LC6000 Free Cooling Unit System
Quick Start Guide
SYSTEM SET-UP
Set up and configuration must be done to each wall-
mount unit using the TEC-EYE hand-held diagnostic tool.
Use the LC6000 controller for the remaining steps.
IMPORTANT:
When working with circuit board
components, Bard recommends the use of
an anti-static wrist strap to prevent static
electricity shorts to electronic controls.
Address each wall unit and select unit zone and unit of
measure (UOM)
The address of the unit being looked at will be listed in
the upper right hand corner on the status screen. The
available addresses are 1-14.
1. Connect TEC-EYE to wall-mount unit.
2. Press MENU key to access the Main Menu screen.
3. Press UP or DOWN keys and ENTER key to enter
password 1313.
4. Press UP or DOWN keys to scroll to
Sys Config
; press
ENTER key.
5. Press ENTER key to scroll to
Unit Address
.
6. Press UP or DOWN keys to change address to value
between 1 and 14.
NOTE:
Each unit must have a unique address for the
communication to work properly. Bard also
recommends labeling each unit for ease in
identification.
7. Press ENTER key to save and scroll to
Unit Zone
.
8. If desired, press UP or DOWN keys to change the
value to the desired zone.
9. Press ENTER key to scroll to
UOM
.
10. If desired, press UP or DOWN keys to change the
value from
USA
to
SI
,
NC
,
LON
,
CAN
or
UK
. Units
are preconfigured for each selection.
11. Press ENTER key to save.
Execute a run test on each unit to verify the equipment is
functioning correctly (TEC-EYE)
1. Use UP or DOWN keys to scroll to
Run Test A11
screen.
2. Press ENTER key to scroll to
Run Test Enable
parameter.
3. Use UP or DOWN key to change value to
ON
. The run
test will begin.
See Installation Instructions 2100-676 if additional
information on run testing units is needed.
Clear unit alarm logs
To clear the wall-mount unit alarm logs:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter
password 1313.
3. Press UP or DOWN keys to scroll to
Settings
; press
ENTER key.
4. Press UP or DOWN keys to scroll to
Initialization
;
press ENTER key.
5. Press UP or DOWN keys to scroll to
Initialization 1/5
;
press ENTER key.
6. Press ENTER key to scroll to
Delete Alarm Logs?
7. Press UP or DOWN key to value to
YES
; press ENTER
key.
After first unit has been set up and configured, follow the
above steps to set up and configure the remaining units.
Set LC Controller Timezone and Date/Time
(LC Controller)
1. Press MENU key to access the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter
password 1313.
3. Press the UP or DOWN keys to scroll to the
Settings
menu; press ENTER key.
4. Press UP or DOWN keys to scroll to
Date/Time
menu;
press ENTER key.
5. Press ENTER key to scroll to the desired value to be
changed.
Manual 2100-677
Date 1-23-18
This quick start guide is designed to lead the installer through the steps necessary for setting up the MULTI-TEC/LC6000
Free Cooling Unit System. See the latest versions of MULTI-TEC/LC6000 System Installation Instructions 2100-676,
MULTI-TEC Service Instructions 2100-665 or LC6000 Service Instructions 2100-669 for more detailed information on
the installation, service and maintenance of the MULTI-TEC/LC6000 system.
The LC6000 controller and TEC-EYE
TM
hand-held diagnostic tool will both be used in this installation. The TEC-EYE
diagnostic tool is shipped inside the controller. Use password 1313.
Содержание MULTI-TEC W18AAPA
Страница 2: ......
Страница 31: ......
Страница 77: ......
Страница 80: ......
Страница 84: ...Manual 2110 1442E Page 4 of 11 FUNCTIONAL COMPONENTS SEXP 177 A 1 10 11 12 5 3 4 8 7 7 2 9 6 13 ...
Страница 99: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369 ...
Страница 100: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368 ...
Страница 105: ......