Manual 2100-665G
Page
15 of 28
To adjust these parameters:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to
Sys Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to
Cooling Setup
(A2)
; press ENTER key.
5. Press ENTER key to scroll to
Stage 1 Diff On
,
Stage 1 Diff Off
,
Stage 2 Diff On
,
Stage 2 Diff Off
,
Stage 3 Diff On
or
Stage 3 Diff Off
(see Figure
19).
6. Press UP or DOWN keys to adjust value.
7. Press ENTER key to save.
Heating Sequence
(see Figure 21)
If the return air temperature is below 58°F (Setpoint
+ Stage 1 Diff On), the unit will enable electric heat
stage 1. If the return air temperature is below 57°F
(Se Stage 2 Diff On), the unit will enable
electric heat stage 2. If the control value is below
56°F (Se Stage 3 Diff On), the unit will enable
electric heat stage 3.
To adjust these parameters:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to
Sys Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to
Heating Setup
(A3)
; press ENTER key.
5. Press ENTER key to scroll to
Stage 1 Diff On
,
Stage 1 Diff Off
,
Stage 2 Diff On
,
Stage 2 Diff Off
,
Stage 3 Diff On
or
Stage 3 Diff Off
(see Figure 20).
6. Press UP or DOWN keys to adjust value.
7. Press ENTER key to save.
FIGURE 21
MULTI-TEC Wall-Mount Unit Heating Staging
On
Band
Off
Stage 2
57
58
59
60
61
62
63
64
65
55
56
Setpoint
Stage 2 Diff On
Stage 2 Diff Off
Stage 1
Stage 1 Diff On
Stage 1 Diff Off
Stage 3
Stage 3 Diff On
Stage 3 Diff Off
FIGURE 19
Adjusting Cooling Differential Values
FIGURE 20
Adjusting Heating Differential Values
Содержание MULTI-TEC W18AAPA
Страница 2: ......
Страница 31: ......
Страница 77: ......
Страница 80: ......
Страница 84: ...Manual 2110 1442E Page 4 of 11 FUNCTIONAL COMPONENTS SEXP 177 A 1 10 11 12 5 3 4 8 7 7 2 9 6 13 ...
Страница 99: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369 ...
Страница 100: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368 ...
Страница 105: ......