Mounting the LC6000 Controller
The dimensions of the LC controller are 16" x 12" x 6".
Because the LC6000 controller utilizes a remote
temperature sensor as opposed to one located in the
controller box, the controller itself can be installed in
any indoor location that is suitable, preferably at eye
level. Four (4) mounting holes are provided for mounting
to the wall and holes for conduit connections are provided
in the base, sides and top of the controller.
The LC6000 controller includes four fused power
supply terminals in the terminal block. Before
connecting wires to the terminal block, confirm that the
fuse in each of the four fuse holders is in the proper
position (active) as shown in Figure 13.
Electrical shock hazard.
Disconnect VAC power supplies before
servicing.
Failure to do so could result in electric shock
or death.
!
WARNING
IMPORTANT:
When working with circuit board
components, Bard recommends the use of
an anti-static wrist strap to prevent static
electricity shorts to electronic controls.
LC6000 Controller
The LC6000 controller is part of this air conditioning
system. It is used to control up to 14 wall-mount air
conditioners from one controller. The microprocessor
control provides an easy-to-read interface with
large LCD graphical display. It provides control for
redundancy for the structure and equal wear on all
units.
Conduit is recommended for all wiring. Route
communication wiring and power supply wiring in their
own separate conduits.
The LC6000 controller is not weatherproof and is
intended for use in a weathertight structure.
FIGURE 13
LC6000 Fused Power Supply Terminal
Shipping Position
Fuse in Active Position
Содержание MULTI-TEC W18AAPA
Страница 2: ......
Страница 31: ......
Страница 77: ......
Страница 80: ......
Страница 84: ...Manual 2110 1442E Page 4 of 11 FUNCTIONAL COMPONENTS SEXP 177 A 1 10 11 12 5 3 4 8 7 7 2 9 6 13 ...
Страница 99: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369 ...
Страница 100: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368 ...
Страница 105: ......