Manual 2100-676D
Page
36 of 45
NOTE:
Screenshots shown in this manual reflect
default settings (when applicable).
The LC6000 controller and TEC-EYE hand-held
diagnostic tool will both be used to set up the Bard air
conditioning system (the TEC-EYE is only used to set
up the wall-mount units).
SYSTEM SET UP
FIGURE 27
TEC-EYE Connection to Unit Control
Modular Connector for TEC-EYE
Hand-Held Diagnostic Tool
The TEC-EYE connects to the wall-mount unit control
board via an RJ11 modular connector as shown in
Figure 27.
When not being used, the TEC-EYE hand-held
diagnostic tool should be stored inside or near the
LC6000 controller. Do not let the TEC-EYE leave the
shelter.
User
2000
Technician
1313
Engineer
9254
Use UP or DOWN keys and ENTER key to enter password
TABLE 5
LC6000/TEC-EYE Passwords (Defaults)
TEC-EYE Hand-Held Diagnostic Tool
The microprocessor control used in the MULTI-TEC
wall-mount air conditioners allows for complete control
and monitoring through the use of the provided TEC-
EYE hand-held monitor.
The menu driven interface provides users the ability
to scroll through two menu levels: Quick Menu and
Main Menu. The menus permit the user to easily view,
control and configure the unit. See the latest version
of MULTI-TEC Service Manual 2100-665 for more
information on using the TEC-EYE.
ALARM KEY
Allows viewing of active alarms
Silences audible alarms
Resets active alarms
MENU KEY
Allows entry to Main Menu
ESCAPE KEY
Returns to previous menu level
Cancels a changed entry
UP KEY
Steps to next screen in the display menu
Changes (increases) the value of a modifiable field
ENTER KEY
Accepts current value of a modifiable field
Advances cursor
DOWN KEY
Steps back to previous screen in the display menu
Changes (decreases) the value of a modifiable field
FIGURE 28
TEC-EYE (Bard P/N 8301-059) Display and Interface (Status Screen Shown)
ALARM KEY
MENU KEY
ESCAPE KEY
DOWN KEY
UP KEY
ENTER KEY
Содержание MULTI-TEC W18AAPA
Страница 2: ......
Страница 31: ......
Страница 77: ......
Страница 80: ......
Страница 84: ...Manual 2110 1442E Page 4 of 11 FUNCTIONAL COMPONENTS SEXP 177 A 1 10 11 12 5 3 4 8 7 7 2 9 6 13 ...
Страница 99: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369 ...
Страница 100: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368 ...
Страница 105: ......