Manual 2100-676D
Page
20 of 45
Model
Rated
Volts &
Phase
No.
Field
Power
Circuits
Single Circuit
Dual Circuit
Minimum
Circuit
Ampacity
Maximum
External
Fuse or
Ckt. Brkr.
Field
Power
Wire
Size
Ground
Wire
Minimum
Circuit
Ampacity
Maximum
External Fuse or
Ckt. Breaker
Field Power Wire
Size
Ground
Wire Size
Ckt.
A
Ckt.
B
Ckt.
C
Ckt.
A
Ckt.
B
Ckt.
C
Ckt.
A
Ckt.
B
Ckt.
C
Ckt.
A
Ckt.
B
Ckt.
C
W36AAEA15
230/208-1
1 or 2
104
110
2
6
52
52
60
60
6
6
10
10
W36AAEB15
230/208-3
1 or 2
66
70
4
8
21
48
30
50
10
8
10
10
W36AAEC15
460-3
1
34
35
8
10
W48AAEA15
230/208-1
1 or 2
110
110
2
6
58
52
60
60
6
6
10
10
W48AAEB15
230/208-3
1 or 2
69
70
4
8
24
49
30
50
10
8
10
10
W48AAEC15
460-3
1
34
35
8
10
W60AAEA15
230/208-1
1 or 3
114
120
2
6
36
52
52
40
60
60
8
6
6
10
10
10
W60AAEB15
230/208-3
1 or 2
72
80
4
8
26
50
30
50
10
8
10
10
W60AAEC15
460-3
1
36
40
8
10
W72ABEA15
230/208-1
1 or 3
134
140
1/0
6
58
52
26
60
60
30
6
6
10
10
10
10
W72ABEB15
230/208-3
1 or 2
83
90
4
8
38
52
40
60
8
6
10
10
W72ABEC15
460-3
1
40
45
8
10
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code
(latest version), Article 310 for power conductor sizing.
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
CAUTION:
When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to
note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a
raceway.
IMPORTANT:
While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor
wires in accordance with the National Electrical Code and all local codes.
TABLE 3
Electrical Specifications
–
W**A*E Series
Содержание MULTI-TEC W18AAPA
Страница 2: ......
Страница 31: ......
Страница 77: ......
Страница 80: ......
Страница 84: ...Manual 2110 1442E Page 4 of 11 FUNCTIONAL COMPONENTS SEXP 177 A 1 10 11 12 5 3 4 8 7 7 2 9 6 13 ...
Страница 99: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369 ...
Страница 100: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368 ...
Страница 105: ......