43 of 45
9. Clear Controller Alarm Logs
The LC6000 controller may have alarms logged
due to bench testing. Controller alarm logs must be
cleared at time of installation.
To clear the LC controller alarm logs:
1) Press MENU key to go to the Main Menu
screen.
2) Use UP or DOWN keys and ENTER key to enter
USER password 2000.
3) Press UP or DOWN keys to scroll to
Settings
;
press ENTER key.
4) Press UP or DOWN keys to scroll to
Initialization
; press ENTER key.
5) Press ENTER key to scroll to
Delete alarm
logs?
(see Figure 45).
6) Press UP or DOWN key to value to
YES
; press
ENTER key.
7) Press ESCAPE key several times to return to
Main Menu screen.
10. Complete Installation
Once all the installation steps have been
completed, all alarms and alarm logs have been
cleared and system verification and run test results
were satisfactory, the installation can now be
considered “complete".
Additional programming information can be found
in MULTI-TEC Service Instructions 2100-665 and
LC6000 Service Instructions 2100-669.
FIGURE 45
Clearing LC6000 Alarm Logs
FIGURE 44
Selecting Economizer Type