TrilliumSeries™ Adiabatic
Cooler - TRF Operation & Maintenance Manual
–
Unit Operation & Storage
Page | 95
Start-up
Control Panel
1.
Verify the correct voltage to the control panel with a meter.
2.
Before power has been provided to the unit, turn all breakers to the On position inside the control panel.
3.
Close the control panel and ensure locks have been fully engaged by rotating 90 degrees on each bolt.
4.
Remove any materials from the sump and ensure the sump access doors are closed and secured.
5.
Turn on breaker or other power supply that supplies power to the unit.
6.
Turn the control panel main disconnect switch to the On position.
Control Settings
7.
Open the HMI cover and wait for the screen to show the home menu in
8.
Navigate to Settings menu, Setup Page shown in
. Confirm correct Language, Date and Time
are selected. If applicable, configure BMS protocol. Refer to
for applicable BMS protocol setup page number.
BMS Protocol
Page Number
Modbus RTU
BACnet MSTP
Modbus TCP
BACnet IP
Table 36. BMS Protocol Setup Page Numbers
9.
If unit is configured as a self-contained unit, navigate to Setpoints menu, Leaving Fluid Control as shown in
. Set
appropriate Operating Mode, Leaving Fluid Temp Setpoint, Control Range, Adiabatic Switchpoint and Run Authorization
Type. Refer to
10.
If unit is configured for a customer control signal, navigate to Setpoints menu, Customer Input Control as shown in
. Set appropriate Operating Mode, Signal Type, Adiabatic Switchpoint, and Run Authorization Type. Refer to
for parameter descriptions.
11.
Navigate to Fans menu shown in
. Press the unit icon on the left of the screen to enter the All Fans menu as
shown in
. Set the appropriate Max Fan Speed and Emergency Fan Speed. Refer to
descriptions.
12.
Navigate to Alarms menu shown in
. Confirm there are no active alarms.
Component Operation
13.
Press
“
Logout
”
in the upper right corner of the screen to navigate to the Login Screen as shown in
. Log in as
Technician. Refer to
Table 8. Access Levels and Passwords
14.
Navigate to Fans menu, Manual as shown in
o
Enter a Manual Setpoint of 100%.
o
Use the radio button to turn Manual Mode to On.
o
In the upper left corner of the screen press
“
Turn On System
”
.
15.
Navigate to Fans menu as shown in
. Press on the picture of each fan and navigate to Analog Data menu to
obtain data for each fan. Verify the fan status and actual speed of each fan.