![Baltimore Aircoil Company TrilliumSeries TRF Скачать руководство пользователя страница 115](http://html1.mh-extra.com/html/baltimore-aircoil-company/trilliumseries-trf/trilliumseries-trf_operation-and-maintenance-manual_3617020115.webp)
TrilliumSeries™ Adiabatic
Cooler - TRF Operation & Maintenance Manual
–
BMS Communication
Page | 115
Variable
Description
R/W
Data
Type
Low
Limit
High
Limit
Modbus
RTU
Registers
BACnet
Addresses
Fan11status
Fan 11 status
0 = Disabled/Offline
1 = Normal
2 = Alarm
R
A
30084
MSO16
Fan11ActlSpd
Fan 11 Speed Feedback in x10
format [RPM]
R
A
30085
AV101
Fan11Pwr
Fan 11 Power in x10 format [kW]
R
A
30086
AV102
Fan11Curr
Fan 11 Current in x10 format [A]
R
A
30087
AV103
Fan11Hrs
Fan 11 run hours [hours]
R
A
30088
AV104
Fan12status
Fan 12 status
0 = Disabled/Offline
1 = Normal
2 = Alarm
R
A
30089
MSO17
Fan12ActlSpd
Fan 12 Speed Feedback in x10
format [RPM]
R
A
30090
AV105
Fan12Pwr
Fan 12 Power in x10 format [kW]
R
A
30091
AV106
Fan12Curr
Fan 12 Current in x10 format [A]
R
A
30092
AV107
Fan12Hrs
Fan 12 run hours [hours]
R
A
30093
AV108
Fan13status
Fan 13 status
0 = Disabled/Offline
1 = Normal
2 = Alarm
R
A
30094
MSO18
Fan13ActlSpd
Fan 13 Speed Feedback in x10
format [RPM]
R
A
30095
AV109
Fan13Pwr
Fan 13 Power in x10 format [kW]
R
A
30096
AV110
Fan13Curr
Fan 13 Current in x10 format [A]
R
A
30097
AV111
Fan13Hrs
Fan 13 run hours [hours]
R
A
30098
AV112
Fan14status
Fan 14 status
0 = Disabled/Offline
1 = Normal
2 = Alarm
R
A
30099
MSO19
Fan14ActlSpd
Fan 14 Speed Feedback in x10
format [RPM]
R
A
30100
AV113
Fan14Pwr
Fan 14 Power in x10 format [kW]
R
A
30101
AV114
Fan14Curr
Fan 14 Current in x10 format [A]
R
A
30102
AV115
Fan14Hrs
Fan 14 run hours [hours]
R
A
30103
AV116
Fan15status
Fan 15 status
0 = Disabled/Offline
1 = Normal
2 = Alarm
R
A
30104
MSO20