10. Unit Operation & Storage
TrilliumSeries™ Adiabatic Products are shipped fully wrapped. If the unit is going to
remain in outdoor storage in excess of
three months prior to installation, remove the stretch wrap and follow the prolonged outdoor storage recommendations listed in
the
TrilliumSeries™ Adiabatic
Cooler
–
TRF Rigging & Assembly Instructions available at
. If you start-up
the unit within three months of delivery, follow the instructions below:
General
•
Use appropriate lockout procedures. Do not perform any service on or near the unit without first ensuring the unit is de-
energized
•
Verify the
unit has been installed according to the TrilliumSeries™ Adiabatic Cooler –
TRF Rigging & Assembly
Instructions available at
Corrosion Protection
BAC products are constructed of corrosion-resistant materials. Materials listed below are used in the equipment construction:
•
Galvanized Steel Components:
Inspect the galvanized steel components for blemishes or corrosion. Wire brush and
recoat the affected areas with a cold galvanizing compound such as zinc rich compound (ZRC).
•
Thermosetting Hybrid Polymer Components:
Inspect the galvanized steel components protected with the
thermosetting hybrid polymer for scratches, scrapes, or blemishes. Cosmetically touch up these areas with color matched
paint.
•
Stainless Steel Components:
Inspect stainless steel components for signs of blemishes or corrosion. See section Long
Term Care of Stainless Steel for cleaning and care instructions.