TrilliumSeries™ Adiabatic
Cooler - TRF Operation & Maintenance Manual
–
BMS Communication
Page | 112
Variable
Description
R/W
Data
Type
Low
Limit
High
Limit
Modbus
RTU
Registers
BACnet
Addresses
PadCleanOverride
Pad Cleaning Override
Use this point to force a pad clean
cycle
0 = Disable
1 = Override
W
B
2854
BV16
CoilCleanOverride
Coil Cleaning Override
Use this point to force a coil clean
cycle
0 = Disable
1 = Override
W
B
2855
BV17
DrainDryOverride
Complete Drain and Dry Override
Use this point to force a drain and
dry cycle
0 = Disable
1 = Override
W
B
2856
BV18
NightDryEn
Night Dry feature Enable
0 = Disabled
1 = Enable
W
B
2857
BV19
ScheduleDryEn
Schedule Dry feature Enable
0 = Disabled
1 = Enable
W
B
2858
BV20
NightQuietEn
Night Quiet feature Enable
0 = Disabled
1 = Enable
W
B
2859
BV21
AlarmCode
Unit Alarm Code
See
R
A
30029
MSO4
FanAlarmCode
Fan Alarm Code
See
R
A
30030
MSO5
AvgFanActlSpd
Average Fan Speed Feedback in
x10 format [RPM]
R
A
30031
AI16
AvgFanPwr
Average Fan Power in x10 format
[kW]
R
A
30032
AI17
AvgFanCurr
Average Fan Current in x10 format
[A]
R
A
30033
AI18
Fan1status
Fan 1 status
0 = Disabled/Offline
1 = Normal
2 = Alarm
R
A
30034
MSO6
Fan1ActlSpd
Fan 1 Speed Feedback in x10
format [RPM]
R
A
30035
AV61
Fan1Pwr
Fan 1 Power in x10 format [kW]
R
A
30036
AV62
Fan1Curr
Fan 1 Current in x10 format [A]
R
A
30037
AV63
Fan1Hrs
Fan 1 run hours [hours]
R
A
30038
AV64
Fan2status
Fan 2 status
0 = Disabled/Offline
1 = Normal
2 = Alarm
R
A
30039
MSO7