TrilliumSeries™ Adiabatic
Cooler - TRF Operation & Maintenance Manual
–
User Interface
Page | 59
Parameter
Description
Night Dry
Enable/Disable
Allows user to either enable or disable the feature. If enabled, no water will be
used during the times set in the schedule shown in
Night Dry Override
If enabled, no water will be used regardless of the schedule shown in
. In
addition to the on-screen button, the override can also be enabled with the
“NightDryOverride” variable in
Table 65. BMS Communication Points List
Night Dry Schedule
The schedule defines a start time on one day and a stop time on the next day. All
times are in 24-hour format.
Table 15. Setpoints Menu, Load Limiting Night Dry Parameters
Figure 45. Setpoints Menu, Load Limiting Page 5 of 6